Bosch D5060 User Manual page 3

Multiplex point programmer

Advertisement

Table 2: Point Type Entry Code
Decimal Value
Point Type
0
Remove point from D8125MUX
1
Contact
2
Sensor (or Single Point Module)
3
I/O Module
4
Mux smoke without low temperature
5
Mux smoke with low temperature
6
Dual point
5. Press [#] to program a point connected to the
D5060 and the D8125MUX (if connected), or
press [1] to program the D8125MUX only. If the
MUX device has DIP switches, program the
device using its DIP switches.
Press [*] at any time to back up through
the sequence.
6. If the point is programmed correctly, the unit
beeps once and displays Adr indicating that it is
ready to program the next point. If the point was
not programmed correctly, the unit sounds a
three-beep error tone and one of the following
messages displays:
The point was not programmed correctly.
Err:
Communications with the D8125MUX
PnL:
failed.
7. Press [*] to clear the entry, or press [#] to
reprogram.
3.3
Removing a Point from the
D8125MUX
1. Apply power to the D5060 and connect the
programmer to the D8125MUX only.
2. Enter the address of the point you wish to
remove.
3. When prompted for a point type, press [0]. Refer
to Table 2.
4.0
Interrogation Mode
You can also use the programmer to read information
from a D8125MUX and from MUX points. Refer to
Section 2.0 Installation for D5060 installation
information.
© Bosch Security Systems B.V., 2021
4.1
Reading Information from the
D8125MUX
1. To put the unit into Interrogation Mode, press
and hold [7] and [9] simultaneously until the unit
beeps. The LED marked INTERROGATION
MODE lights.
2. The display shows A.dr and the left-most
decimal point lights, prompting the user to enter a
starting address. Enter an address followed by [#].
3. The Interrogation LED flashes. Press [#] to read
point information from the D8125MUX at that
address.
4. Press [4] to read the previous address information
from the D8125MUX.
5. Press [6] to read the next address information
from the D8125MUX.
If communication between the unit and the
D8125MUX fails, the unit sounds a three-
beep error tone and displays PnL.
6. To exit Interrogation Mode, press and hold [*]
until the unit beeps.
4.2
Reading Information from MUX
Points
Disconnect all multiplex points from the
D8125MUX and the multiplex bus before
reading multiplex point information.
1. To put the unit into Interrogation Mode, press
and hold [7] and [9] simultaneously until the unit
beeps. The LED marked INTERROGATION
MODE lights.
2. The display reads A.dr and the left-most decimal
point lights, prompting you to enter a starting
address. Enter an address and press [#].
3. Press [1].
4. When t.YP displays at the keypad, enter the
point type of the Mux point (Table 2) and press
[#].
5. If a point responds to the address, the
programmer beeps once and displays rSP. If the
point does not respond, the unit beeps three times
and the display reads noP.
6. To exit Interrogation Mode, press and hold [*]
until the unit beeps.
D5060 User's Guide
Page 3
D5060
F01U034899-02