(1) Hourly data
Counter or analog integration is integrated for one hour (60 samples) of historical tag data
collected in one-minute periods in accordance with the tag type set up in the report database.
Save the integration results with report tags as hourly data.
1) Counter
Calculate and total differences between nth data and n-1th data of historical tag data
collected in one-minute periods.
2) Analog integration
Convert and total historical tag data collected in one-minute periods in accordance with
the time conversion coefficient set up with the historical tag.
3) Operation time
The ON time of digital tag signals is integrated.
4) Halt time
The OFF time of digital tag signals is integrated.
(2) Daily data
The day maximum value, day maximum value time, day minimum value, day minimum
value time, day average value and day total value for one day (24 samples) of hourly data are
calculated and the calculation results are saved with report tags as daily data.
(3) Monthly data
The month maximum value, month maximum value time, month minimum value, month
minimum value time, month average value and month total value for one month (31 samples)
of day total values of daily data are calculated and the calculation results are saved with
report tags as monthly data.
(4) Yearly average system
The year maximum value, year maximum value time, year minimum value, year minimum
value time, year average value and year total value for one year (12 samples) of monthly total
values of monthly data are calculated and the calculation results are saved with report tags as
yearly data.