System Set Up
Service Menu
The service menu provides functions for use by installer or service engineer. It is NOT intended the home owner alters settings within this menu. It is for this reason
password protection is required to prevent unauthorised access to the service settings.
The factory default password is "0000".
Follow the procedure described in General Operation for the set up operation.
Many functions can not be set whilst the indoor unit is running. The installer should turn off the unit before trying to set these functions. If the installer attempts to change
the settings whilst the unit is running the main remote controller will display a reminder message prompting the installer to stop operation before continuing. By selecting
"Yes" the unit will cease operation.
<Manual operation>
During the filling of the system the primary circuit circulation pump can be manually overridden using
manual operation mode.
When manual operation is selected a small timer icon appears in the screen. When selected, this
function will only remain in manual operation for a maximum of 2 hours. This is to prevent accidental
permanent override of the FTC.
Manual operation and heat source setting can not be selected if the system is running.
A screen will be displayed asking the installer to stop the system before these modes
can be activated.
<Auxiliary settings>
This function is used to set the parameters for any auxiliary parts used in the system
Menu subtitle
Function/ Description
Economy settings for
Water pump stops automatically a specified period of time from when operation is
pump
finished.
Delay
Time before pump switches off*1
Electric heater
To select "WITH booster heater (ON)" or "WITHOUT booster heater (OFF)" in
(Heating)
Heating mode.
Delay
The minimum time required for the booster heater to turn ON after Heating mode
has started.
Flow
Minimum The minimum flow rate to be detected at flow sensor.
sensor *2
Maximum The maximum flow rate to be detected at flow sensor.
*1. Decreasing "time before pump switched off" may increase the duration of stand-by in heating mode.
*2. Do not change the setting since it is set according to the specification of flow sensor attached to the Hydro
box.
<Heat source setting>
The default heat source setting is heat pump and all electric heaters present in the system to be operational.
This is referred to as standard operation on the menu.
<Operation settings>
Heating operation
This function allows operational setting of flow temperature range from the Ecodan and also the time interval at which the FTC collects and processes data for the auto
adaptation mode.
Menu subtitle
Flow temp. range
Minimum temp.
Maximum temp.
Room temp. control
Mode
Interval
Heat pump thermo diff.adjust
On/Off
Lower limit
Upper limit
Note:
1. The minimum flow temperature that prohibits heat pump operation is 20ºC.
2. The maximum flow temperature that allows heat pump operation equals to the maximum temperature set in the Flow temp. range menu.
* Fast mode is not efficient and will increase running cost when compared to normal mode.
Function
To minimize the loss by frequent ON and OFF in mild outdoor ambient tem-
perature seasons.
To set max. possible flow temperature according to the type of heat emitters. 35 - 60
Setting for Room temp. control
At Fast mode, target outlet water temperature is set higher than the one set
at normal mode. This reduces the time to reach the target room temperature
when the room temperature is relatively low.*
Selectable according to the heat emitter type and the materials of floor (i.e.
radiators, floor heating-thick, -thin concrete, wood, etc.)
To minimize the loss by frequent ON and OFF in mild outdoor ambient tem-
perature seasons.
Prohibits heat pump operation until the flow temperature drops below the
target flow temperature plus lower limit value.
Allows heat pump operation until the flow temperature rises above the target
flow temperature plus upper limit value.
<Table 5.6.1> Heating operation(Room temp.control table)
Selected Running
Manual operation menu screen
Auxiliary settings menu screen
Range
25 - 45
Normal/
Fast
10 - 60
On/Off
−9 - −1
+3 - +5
* When an error
occurs, the icon
indicates as below.
Error
indication
en
Unit
Default
ºC
30
ºC
50
Normal
min
10
On
ºC
−5
ºC
+5
20