Hitachi WJ200-004MF Manual page 18

Table of Contents

Advertisement

Function List
Code
C041
Overload level setting
C241
Overload level setting, 2nd motor
C042
Frequency arrival setting for acceleration
C043
Frequency arrival setting for deceleration
C044
PID deviation level setting
C045
Frequency arrival signal for acceleration (2)
C046
Frequency arrival signal for deceleration (2)
C047
Pulse train input scale conversion for EO output
C052
PID FBV function high limit
C053
PID FBV function variable low limit
C054
Over-torque / under-torque selection
C055
Over / under-torque level (Forward powering mode)
C056
Over / under-torque (Reverse regen. mode)
C057
Over / under-torque (Reverse powering mode)
C058
Over / under-torque level (Forward regen. mode)
C059
Signal output mode of Over / under torque
C061
Electronic thermal warning level setting
C063
Zero speed detection level setting
C064
Heat sink overheat warning
C071
Communication speed selection
C072
Node allocation
C074
Communication parity selection
C075
Communication stop bit selection
C076
Communication error select
C077
Communication error time-out
C078
Communication wait time
C081
O input span calibration
C082
OI input span calibration
C085
Thermistor input (PTC) span calibration
C091
00 (Disable) / 01 (Enable)
C096
Communication selection
C098
EzCOM start adr. of master
C099
EzCOM end adr. of master
C100
EzCOM starting trigger
C101
UP / DWN memory mode selection
C102
Reset selection
C103
Restart mode after reset
C104
UP / DWN clear: terminal input mode selection
C105
EO gain adjustment
C106
AM gain adjustment
C109
AM bias adjustment
C111
Overload setting (2)
C130
Output 11 on-delay time
C131
Output 11 off-delay time
C132
Output 12 on-delay time
C133
Output 12 off-delay time
C140
Output RY on-delay time
C141
Output RY off-delay time
C142
Logical output signal 1 selection 1
C143
Logical output signal 1 selection 2
C144
Logical output signal 1 operator selection
C145
Logical output signal 2 selection 1
C146
Logical output signal 2 selection 2
C147
Logical output signal 2 operator selection
C148
Logical output signal 3 selection 1
C149
Logical output signal 3 selection 2
C150
Logical output signal 3 operator selection
C160 – C166 Response time of intelligent input terminal 1 – 7
C169
Multistage speed / position determination time
 18
Function Name
Set range: 0 to 200% of inverter rated current [A]
Set range: 0 to 200% of inverter rated current [A]
0.00 to 99.99 / 100.0 to 400.0 [Hz]
0.00 to 99.99 / 100.0 to 400.0 [Hz]
0.0 to 100.0 [%]
0.00 to 99.99 / 100.0 to 400.0 [Hz]
0.00 to 99.99 / 100.0 to 400.0 [Hz]
0.01 to 99.99
0.0 to 100.0 [%]
0.0 to 100.0 [%]
00 (Over torque) / 01 (under torque)
0 to 200 [%]
0 to 200 [%]
0 to 200 [%]
0 to 200 [%]
00 (output during acceleration / deceleration and constant-speed operation) /
01 (output only during constant-speed operation)
0 to 100 [%]
0.00 to 99.99 / 100.0 [Hz]
0. to 110. [
03 (2400bps) / 04 (4800bps) / 05 (9600bps) / 06 (19200bps) / 07 (38400bps) /
08 (57600bps) / 09 (76800bps) / 10 (115200bps)
1 to 247
00 (no parity) / 01 (even parity) / 02 (odd parity)
1 (1bit) / 2 (2bit)
00 (tripping) / 01 (tripping after decelerating and stopping the motor) /
02 (ignoring errors) / 03 (stopping the motor after free-running) /
04 (decelerating and stopping the motor)
0.00 to 99.99 [s]
0 to 1000 [ms]
0. to 200.0 [%]
0. to 200.0 [%]
0. to 200.0 [%]
00
00 (Modbus-RTU) / 01 (EzCOM) / 02 (EzCOM [administrator])
01 to 08
01 to 08
00 (Input terminal) / 01 (Always)
00 (not storing the frequency data) / 01 (storing the frequency data)
00 (resetting the trip when RS is on) / 01 (resetting the trip when RS is off) /
02 (enabled resetting only upon tripping [resetting when RS is on]) /
03 (resetting only trip)
00 (starting with 0 Hz) / 01 (starting with matching frequency) /
02 (restarting with active matching frequency)
00 (0Hz) / 01 (EEPROM data when power supply is turned on)
50 to 200 [%]
50 to 200 [%]
0 to 100 [%]
Set range: 0 to 200% of inverter rated current [A]
0.0 to 100.0 [s]
0.0 to 100.0 [s]
0.0 to 100.0 [s]
0.0 to 100.0 [s]
0.0 to 100.0 [s]
0.0 to 100.0 [s]
Same as the settings of C021 to C026 (except those of LOG1 to LOG3 & OPO, no)
00 (AND) / 01 (OR) / 02 (XOR)
Same as the settings of C021 to C026 (except those of LOG1 to LOG3 & OPO, no)
00 (AND) / 01 (OR) / 02 (XOR)
Same as the settings of C021 to C026 (except those of LOG1 to LOG3 & OPO, no)
00 (AND) / 01 (OR) / 02 (XOR)
0 to 200 ( × 2ms)
0. to 200. (× 10ms)
Setting Range
º
C]
[ ○ = Allowed × = Not parmitted]
Setting During
Change During
Default
Operation
Operation
Setting
(allowed or not)
(allowed or not)
115% of
Rated current
115% of
Rated current
×
0.00
×
0.00
×
3.0
×
0.00
×
0.00
1.00
×
100.0
×
0.0
×
00
×
100
×
100
×
100
×
100
×
01
×
90
×
0.00
×
100
×
05
×
1
×
00
×
1
×
02
×
0.00
×
0
100.0
100.0
100.0
00
×
×
00
×
×
01
×
×
01
×
×
00
×
00
00
×
00
×
00
100
100
0
115% of
Rated current
×
0.0
×
0.0
×
0.0
×
0.0
×
0.0
×
0.0
×
00
×
00
×
00
×
00
×
00
×
00
×
00
×
00
×
00
×
1.
×
0.