For example, if there is a configuration to use IEC 61850 9–2 analog data, but no data arrives on the
access point, then the IED will use substituted data and most protection functions will be blocked. This
condition will be indicated with a sub-menu under Hints, where details about this condition are shown.
The Hint menu is a way to assist the user in troubleshooting.
The supported list of hints are as follows:
Table 29:
Headline
Incorrect setting of SyncLostMode
Sampled value substituted
Time diff: IED vs Sampled value
Frequency diff: IED vs Sampled value
Wrong cycle time for PMU report
PMU not connected to 3ph output
Invalid value set for PMU Parameters
Invalid phase angle reference
Table continues on next page
Bay control REC670
Commissioning manual
The Hint menu is currently only available in English. All the entries are in English,
regardless of which language is selected.
Hint menu
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Explanation
There are two explanations possible:
SyncLostMode is set to Block, no time source is configured
to achieve the required accuracy. Unless a high accuracy
time source is selected, the function dependent on high
time accuracy will be blocked.
SyncLostMode is set to BlockOnLostUTC, but there is no
UTC capable synch source (GPS, IRIG-B) used. Unless a
UTC capable time source is selected, the function
dependent on high time accuracy will be blocked.
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as given
in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi Power
grids_MU0101>
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as given
in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi Power
grids_MU0101>
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as given
in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi Power
grids_MU0101>
Wrong cycle time on SMAI or 3PHSUM block connected to
Phasor Report block. The SMAI or 3PHSUM block should
have same cycle time as that of Phasor Report.
The PMU phasor report input(s) must be connected to the
3ph output of SMAI or 3PHSUM.
There are two possible error conditions:
Check if the following parameters are set correctly on
PMUREPORT:1 ReportRate or SvcClass or parameter
PRIMVAL:1.FrequencySel is not set as 50Hz / 60Hz.
Check if the following parameters are set correctly on
PMUREPORT:1 ReportRate or SvcClass or RptTimetag or
parameter PRIMVAL:1.FrequencySel is not set as 50Hz /
60Hz.
The selected PhaseAngleRef corresponds to an analog
channel that is not configured. Configure a valid reference
channel.