Huawei NetCol8000-A Series Quick Manual page 24

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A Series:
Table of Contents

Advertisement

1. First startup flowchart
Start
Tap Start on the home screen.
After tapping Yes, the barcode and the
verification code are shown on the screen.
Open the Service Expert app.
Tap StartUp > Offline Activation on APP
Enter Bar code and Verification code,
and tap Generate PWD.
Enter the generated startup password on
the screen of smart cooling product.
Tap Enter. The screen turns to Wizard
Startup.
Refrigerant is fully charged?
No
Tap No on Wizard Startup screen to exit
wizard startup.
Tap Start on the home screen and choose
Maint > Diagnostic Mode > Enter.
Set the compressor to 3000 rpm.
Charge the remaining amount of
refrigerant from low-pressure needle
valve.
Choose Maint > Diagnostic Mode > Exit
and tap Shutdown on the home
screen.
Choose Maint > Wizard Startup to enter
wizard startup.
Go to step 2
2. Wizard startup flowchart
Start
Precautions
Yes
Select commissioning items
Yes
Indoor fan commissioning
Success
Outdoor fan commissioning
Success
Electric heater
commissioning
Success
Humidifier commissioning
Success
Cooling system
commissioning
Success
End
Yes
Tap Yes on
Wizard Startup
screen to enter
wizard startup.
24
No
Fail
Commissioning
interrupted
Fail
(Handle the
fault by
Fail
referring to the
tips displayed
on the home
Fail
screen.
Perform wizard
startup after
Fail
the handling.)
Fail
If there is no water supply,
clear the humidifier
commissioning item when
wizard startup
commissioning. After
Wizard startup, lift the low
liquid level detector. After at
least 5 seconds, choose
Running > Device Details
> Humidifier to check that
Low liquid level states is
Triggered. Choose
Running > Device Details
> Humidifier > Advanced
to check that Humidifier
pump control states is On.