Access Modular Controller 2
4.10

RS-232 Host Interface

The AMC2 offers an RS-232 serial interface to connect a host computer or serial modem.
Notice!
Risk of malfunction
Cable length between two RS-232 COM serial interfaces must not exceed 15 meters (45 ft).
Figure 4.13: Location of the RS-232 serial interface
As the AMC2 controller is conceptionally a PC, it is not possible to connect them directly using
normal cables. Use instead a null modem or "crossover" cable. A complete connection
diagram of the RS-232 host interface is shown in chapter Connecting Diagrams, page 43