ABB COM600 3.4 User Manual page 30

Station automation, iec 60870-5-101 master (opc)
Hide thumbs Also See for COM600 3.4:
Table of Contents

Advertisement

30
Station Automation COM600 3.4
IEC 60870-5-101 Master (OPC) User's Manual
Name
Unrecognized Message Hand-
ling
Lengths
Cause of Transmission Length
Information Address Length
Maximum Message Length
Polling Address Length
Station Address Length
Time Handling
Disable Hour Change Clock
Message
Time Synchronization Interval
Time Synchronization Offset
Value/Value range
True
False
Default: False
1...2
Default: 1
1...3
Default: 2
20...255
Default: 230
0...2
Default: 1
1...2
Default: 1
True
False
Default: False
0...65535
Default: 15
-32768...32767
1MRS756703
Description
Handling of the unrecognized
messages. When this is false,
unrecognized messages are
ignored. When this is true,
unrecognized messages sent
by the slave are forwarded to
an object with an address
defined by the Unrecognized
Messages Address property.
The length of the cause of
transmission field in an IEC
60870-5-101 message in oct-
ets.
The length of the information
object address in octets.
The maximum length of trans-
mitted message in octets.
The length of the polling
address in octets.
The length of the station
address in octets.
The hour transmission method
of the events to the master.
When this is false, the master
gets the year, date, and hour
from the slave as hourly clock
synchronization (ASDU 103).
When this is true, the master
adds the year, date, and hour
from its internal clock to the
events. Minutes and seconds
should be provided in time-
tagged events by the slave.
Time synchronization interval
in seconds.
Time synchronization offset in
tenth of milliseconds. This can
be used to fine-tune the time
synchronization accuracy,
when there is a fixed delay
caused by the used communic-
ation network.