Table 6- 15
Terminal module TPRo with relays for outputs
6ES7924-0BD20-0Bx0
Energizing side
Operating voltage for coil
Input circuit
Contact side
Number of relay outputs
Contact design
Switching capacity (resistive load)
Switching frequency
Service life
Mechanical
Electrical
Inductive loads
Connection to SIMATIC fitted for
Operating temperate
Mounting position
Clearances and creepage distances
Dimensions (W x H x D) in mm
6ES7924-0BG20-0Bx0
SIMATIC TOP connect for S7-1500 and ET200MP
Manual,
Technical specifications for terminal module TPRo
6.7 Technical specifications for terminal modules
24 V DC 19 - 28.8 V
Reverse polarity protection and freewheeling
diodes
8 NO contacts
Single contact, 1 NO contact
max. 4 A / 250 V AC
max. 3 A / 30 V DC
max. 0.6 A / 48 V DC
max. 0.4 A / 60 V DC
Recommended minimum load ≥ 1 mA
6 cycles/minute
3 x 10
switching cycles
6
5 x 10
switching cycles at 230 V AC/4 A/ cos φ =
4
1, 6 x per minute
To protect the relay contacts, inductive loads
must be dampened externally with an effective
protective circuit. No measures are provided for
this in the TPR.
16-pin IDC connector with fitted strain relief
0 ... +60° C
Any
IEC 60664-1, IEC61131-2,
CSA C22.2 No 142 UL 508, VDE 0160,
overvoltage category II,
pollution degree 2
Approx. 100 x 76 x 60
Technical specifications
63