3.2. Status indicator

3.2.1.
On the option
The PDP003Z has two LEDs, ST (Status) and DX (Data exchange) to indicate the
statuses of PROFIBUS-DP and the PDP003Z itself.
ST (Status)
DX (Data exchange)
ST (Status): Red LED
LED
Flashes
Lights
DX (Data exchange): Green LED.
The status of the PROFIBUS network is indicated.
It lights when the PDP003Z is on-line and data exchange is possible.
3.2.2.
On the inverter
When PROFIBUS option is used, please attach the LED label for PROFIBUS option to
lower side of communication indicator of VF-AS3.
ST (Status) is displayed to the NET2-LED together on communication indicator.
Off
No diagnostics present
8 Hz (Blinking 4 times/1sec.):
Waiting for parameterization or configuration
2 Hz (Blinking 1 times/1sec.):
PDP003Z station address is "126".
(Refer to 5 section.)
DP status error
* For example, a station address is not set correctly.
Meanings
- 9 -
E6581738④