Advertisement

Error code
Clear text
Loc: 225
PWM fan faulty
Loc: 226
PWM fan faulty
Loc: 227
PWM fan faulty
Error in compatibility between PME7 and
rSt Er1
LME7 during restore process
Error in compatibility between PME7 and
rSt Er2
LME7 during restore process
rSt Er3
Error during restore process
Error in compatibility between PME7 and
bAC Er3
LME7 during backup process
Err PrC
Error in PME7
Smart Infrastructure
Basic Documentation LME7...
14 Error code list with operation via external AZL2 display
Possible cause
- After the prepurge speed was reached, the
minimum PWM prepurge speed was undercut
(parameter 675.00) or ...
- After reaching the ignition load speed, the
maximum ignition load PWM (parameter 675.01)
was exceeded
Parameterization error:
- Speed low-fire > speed high-fire, or
- Low-fire = 0 rpm, or
- Maximum speed = 0 rpm
One or several parameters violate the minimum /
maximum limit
Program sequence of PME7 does not match the
LME7
LME7 hardware does not match the PME7
PME7 faulty
PME7 removed during restore process
Program sequence of PME7 does not match the
LME7
Data content of the PME7 defective
No PME7 plugged in