Download Print this page

Siemens 3AH3 Instruction Manual page 53

Vacuum circuit breaker operator modules 4.16 kv to 38 kv

Advertisement

Table 12:Type 3AH vacuum circuit breaker ratings (historic "constant MVA" ratings basis)
Nominal
voltage
class
Circuit
breaker type
kV
5-3AH-250,
4.16
5-3AHc-250
5-3AH-350,
4.16
5-3AHc-350
7-3AH-500
7.2
15-3AH-500
13.8
15-3AH-750
13.8
15-3AH-1000
13.8
38-3AH-1500
38.0
Footnotes:
Maximum design voltage for which the circuit
1.
breaker is designed and the upper limit for
operation.
K is the ratio of the rated maximum design
2.
voltage to the lower limit of the range of
operating voltage in which the required
symmetrical and asymmetrical interrupting
capabilities vary in inverse proportion to the
operating voltage.
To obtain the required symmetrical interrupting
3.
capability of a circuit breaker at an operating
voltage between 1/K times rated maximum
design voltage and rated maximum design
voltage, the following formula shall be used:
Required symmetrical interrupting capability =
rated short-circuit current (I) x [(rated maximum
design voltage)/(operating voltage)]. For
operating voltages below 1/K times maximum
design voltage, the required symmetrical
interrupting capability of the circuit breaker shall
be equal to K times rated short-circuit current.
Nominal
Maximum
three-
design
Continuous
phase
voltage
current
MVA
(V)
1
class
7
MVA
kV rms
A rms
250
4.76
1,200, 2,000
1,200,
350
4.76
2,000, 3,000
1,200,
500
8.25
2,000, 3,000
1,200,
500
15.0
2,000, 3,000
1,200,
750
15.0
2,000, 3,000
1,200,
1000
15.0
2,000, 3,000
1,500
38.0
1,200, 2,000
Within the limitations stated in
4.
ANSI/IEEE C37.04-1979, all values apply to
polyphase and line-to-line faults. For single
phase-to-ground faults, the specific conditions
stated in clause 5.10.2.3 of
ANSI/IEEE C37.04-1979 apply.
Current values in this row are not to be exceeded
5.
even for operating voltage below 1/K times rated
maximum design voltage. For operating voltages
between rated maximum design voltage and 1/K
times rated maximum design voltage, follow
Footnote 5.
Current values in this row are independent of
6.
operating voltage up to and including rated
maximum voltage.
"Nominal three-phase MVA class" is included for
7.
reference only. This information is not listed in
ANSI C37.06-1987.
Standard duty cycle is O - 15 s - CO.
8.
Standard rating interrupting time is five-cycles
9.
(83 ms). Optional rated interrupting time of
three-cycles (50 ms) is available (except with
24 Vdc tripping).
Voltage
range
Withstand voltage
factor
levels
11
(K)
2
Power
----
frequency
kV rms
1.24
19
1.19
19
1.25
36
1.30
36
1.30
36
1.30
36
1.65
80
These ratings are in
accordance with:
ANSI/IEEE C37.04-1979
Standard Rating Structure
for AC High-Voltage Circuit
Breakers Rated on a
Lightning
impulse
Symmetrical Current Basis
(BIL)
ANSI C37.06-1987 AC
kV crest
High-Voltage Circuit
Breakers Rated on a
60
Symmetrical Current Basis -
Preferred Ratings and
Related Required
60
Capabilities
ANSI/IEEE C37.09-1979
Standard Test Procedure for
95
AC High-Voltage Circuit
Breakers Rated on a
Symmetrical Current Basis
95
ANSI/IEEE C37.010-1979
Application Guide for AC
High-Voltage Circuit
95
Breakers Rated on a
Symmetrical Current Basis.
95
150
High close and latch
10.
(momentary) rating available for
special application.
Continuous current may be
11.
increased by the use of forced-
cooling (fan-cooling) in the
switchgear, together with
increased bus bar capacity.
53

Advertisement

loading

This manual is also suitable for:

3ahc