LG MULTI V WATER MINI Engineering Manual page 57

Table of Contents

Advertisement

Water Source Unit DIP Switch Settings
Table 26: Water Source Unit DIP Switch Settings.
ON
OFF
1 2
3 4 5
• After the DIP switch is changed, the reset switch must be pressed to reflect the setting.
• Before operating the water source unit, check the water flow rate and the PCB voltage signal.
• Minimum flow rate range is 50%; Reference flow rate: 4.4-ton - 15.9 gpm.) When the Variable Water Flow Control kit is also installed, set
the flow switch minimum flow rate to 40% of the nominal flow rate instead of 50%. If the flow rate is lower, it will damage the water source
unit.
WATER CIRCUIT INSTALLATION
Variable Water Flow Control Kit (Required Accessory)
SW01B
ON
OFF
1 2
3 4 5
6 7
DIP Switch Setting
ON
OFF
6 7
1 2
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
SW02B
ON
OFF
1 2
3 4 5
6 7
3 4 5
6 7
Function
Variable Water Flow Control Mode
WATER CIRCUIT | 57