Supply & Load Cable Connections - Philips Dynalite DLE1210 Installation Manual

12 x 10a leading edge dimmer
Table of Contents

Advertisement

supply & load cable connections
Supply Cables
The supply input terminals are located toward
the top of the enclosure and consists of Earth,
Neutral, and Phase, all of which will accept up to
2
25mm
cables. The supply cables should have
a capacity of 40A per phase, to allow the device
to be loaded to its maximum capacity.
Load Cables
Load cables can be terminated on a Load &
Neutral terminal strip, one pair for each channel,
and an Earth link located at the centre of the
enclosure. These connectors will accept up to
6mm
cables. Calculate the intended load, and
2
ensure that it is below the maximum capacity of
an individual channel, which is 10A. Do not use
a common neutral at a remote location.
.
Emergency Lighting Connections
Connect emergency lighting circuit active to the
load side on the circuit breaker for the relevant
channel, as indicated by the labels next to the
circuit breakers. Do not remove any cables that
may already be terminated at this location.
Energising the Device
If it is necessary to energise load circuits before
any
control
acceptable to replace the cover and energise
the device immediately, as the default factory
programming is to have all channels set to 100%
output.
If there is no output on any or all
channels, see the "Troubleshooting" section
(page 8). This device should be de-energised
before terminating the control and data cables.
cables
are
connected,
DLE1210 Installation Manual Rev G.docx
it
is
5