Panasonic WH-MXC09G3E5 Service Manual page 5

(mono bloc) air-to-water heatpump system
Hide thumbs Also See for WH-MXC09G3E5:
Table of Contents

Advertisement

Input Power
Maximum Input Power For Mono bloc Unit
Power Supply 1: Phase (ø) / Max. Current (A) / Max. Input Power (W)
Power Supply 2: Phase (ø) / Max. Current (A) / Max. Input Power (W)
Power Supply 3: Phase (ø) / Max. Current (A) / Max. Input Power (W)
Starting Current
Running Current
Maximum Current For Mono bloc Unit
Power Factor
Power factor means total figure of compressor and outdoor fan motor.
Power Cord
Thermostat
Protection Device
Performance Test Condition
Operation Range
Internal Pressure Differential
Water Pipe Diameter
Water Drain Hose Inner Diameter
Pump
Hot Water Coil
Pressure Relief Valve Water Circuit
Flow Switch
Protection Device
Expansion Vessel
Capacity of Integrated Electric Heater
Note:
1.
Cooling capacities are based on outdoor air temperature of 35°C Dry Bulb with controlled water inlet temperature of 12°C and water outlet
temperature of 7°C.
2.
Heating capacities are based on outdoor air temperature of 7°C Dry Bulb (44.6°F Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb) with controlled
water inlet temperature of 30°C and water outlet temperature of 35°C.
3.
Specifications are subjected to change without prior notice for further improvement.
Item
Number of core
Length
Item
Outdoor Ambient
Water Outlet
Inlet
Outlet
Motor Type
No. of Speed
Input Power
Type
No. of Plates
Size (H × W × L)
Water Flow Rate
Volume
MWP
Unit
kW
kW
A
A
A
%
m (ft)
Unit
°C
°C
kPa
mm (inch)
mm (inch)
mm (inch)
W
mm
3
l/min (m
/h)
kPa
A
I
bar
kW
6
Mono bloc Unit
Cooling: 2.21
Cooling: -
Heating: 1.86
Heating: 2.51
5.41
Single / 25.0 / 5.41k
Single / 13.0 / 3.00k
- / - / -
10.2
Cooling: 10.2
Cooling: -
Heating: 8.6
Heating: 11.6
25.0
Cooling: 94
Cooling: -
Heating: 94
Heating: 94
-
-
Electronic Control
Electronic Control
Water System
EN14511
Cooling: 16 ~ 43
Heating: -20 ~ 35
Cooling: 5 ~ 20
Heating: 25 ~ 55
Cooling: 14.3
Heating: 22.8
30 (1-3/16)
30 (1-3/16)
15.00 (19/32)
DC Motor
7 (software selection)
50
Brazed Plate
36
65 × 120 × 376
Cooling: 20.1 (1.2)
Heating: 25.8 (1.5)
Open: 300, Close: 265 and below
Magnetic Lead Switch
Residual Current Circuit Breaker (30)
10
3
3.00

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-mxc12g6e5

Table of Contents