8. Electric Characteristicss
Model
Type
ARNU05GTR*4
TR
ARNU07GTR*4
TR
ARNU09GTR*4
TR
ARNU12GTR*4
TR
ARNU15GTQ*4
TQ
ARNU18GTQ*4
TQ
ARNU21GTQ*4
TQ
ARNU24GTP*4
TP
ARNU28GTP*4
TP
ARNU30GTP*4
TP
ARNU36GTN*4
TN
ARNU42GTM*4
TM
ARNU48GTM*4
TM
ARNU54GTM*4
TM
ARNU05GTR*4
TR
ARNU07GTR*4
TR
ARNU09GTR*4
TR
ARNU12GTR*4
TR
ARNU15GTQ*4
TQ
ARNU18GTQ*4
TQ
ARNU21GTQ*4
TQ
ARNU24GTP*4
TP
ARNU28GTP*4
TP
ARNU30GTP*4
TP
ARNU36GTN*4
TN
ARNU42GTM*4
TM
ARNU48GTM*4
TM
ARNU54GTM*4
TM
Symbols:
MCA : Minimum Circuit Amperes (A)
MFA : Maximum Fuse Amperes(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amperes(A)
IFM : Indoor Fan Motor
Units
Hz
Volts
Voltage Range
Max:264
50
220-240
Min:198
Max:242
60
220
Min:198
Power Supply
MCA
MFA
kW
0.25
15
0.043
0.25
15
0.043
0.25
15
0.043
0.25
15
0.043
0.25
15
0.043
0.25
15
0.043
0.25
15
0.043
0.19
15
0.030
0.19
15
0.030
0.19
15
0.030
0.71
15
0.135
1.60
15
0.135
1.60
15
0.135
1.60
15
0.135
0.25
15
0.043
0.25
15
0.043
0.25
15
0.043
0.25
15
0.043
0.25
15
0.043
0.25
15
0.043
0.25
15
0.043
0.19
15
0.030
0.19
15
0.030
0.19
15
0.030
0.71
15
0.135
1.60
15
0.135
1.60
15
0.135
1.60
15
0.135
Note :
1. Voltage Range
Units are suitable for use on electrical system where
voltage supplied to unit terminals is not below or
above the listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MCA/MFA
MCA = 1.25 x FLA
MFA ≤ 4 x FLA
( Next lower standard fuse rating. Minimum 15A)
4. Select wire size based on the larger value on the MCA.
5. Instead of fuse, use Circuit Breaker.
Ceiling Cassette 4-way
IFM
Input(W)
FLA
Cooling Heating
0.20
30
30
0.20
30
30
0.20
30
30
0.20
30
30
0.20
30
30
0.20
30
30
0.20
30
30
0.15
40
40
0.15
40
40
0.15
40
40
0.56
144
144
1.30
144
144
1.30
144
144
1.30
144
144
0.20
30
30
0.20
30
30
0.20
30
30
0.20
30
30
0.20
30
30
0.20
30
30
0.20
30
30
0.15
40
40
0.15
40
40
0.15
40
40
0.56
144
144
1.30
144
144
1.30
144
144
1.30
144
144
_ 31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multi v arnu09gtua4Multi v arnu12gtua4Multi v arnu18gtta4Multi v arnu24gtta4Multi v arnu09gtla4Multi v arnu12gtla4 ... Show all

Table of Contents