Siemens RDJ100 Series Quick Manual page 2

Advertisement

Reset service reminder
·
Set programming selector to position
·
Press advance button for about 5 seconds until the display
goes blank. Turn setting knob, screen display will be:
o 1
o 2
·
Press advance button once and the 2
and is ready for adjustment.
·
Optional. Adjust the days of next service due day (1...400
days) by turning setting knob.
·
Press advance button once to confirm the setting.
Note: If service due day is set to "OFF", thermostat will go
back to normal operation (time setting position
·
The display will show:
o 1
o 2
·
Optional. Adjust pre-warning time to 0...50 days by turning
setting knob.
·
Press advance button once to confirm the setting.
·
The display will show:
o 1
o 2
·
Optional. Adjust service interval action by turning setting
knob:
o 0: warning only
o 1: 60 mins control with Comfort temperature
·
Press advance button once to confirm setting and go back to
normal operation.
Set programming selector to RUN position.
A6V11239600_en--_a
.
st
line: "SEr"
nd
line: the days of next service due day (1...400 days).
nd
line starts flashing
st
line: "PrE"
nd
line: "28d"
st
line: "Act"
nd
line: "1"
2018-06-22
Subject to alteration
Disable service reminder
).
Note: The timeout of service interval reminder setting is one minute.
·
Set programming selector to position
·
Press advance button for about 5 seconds until the display
goes blank. Turn setting knob, screen display will be:
st
o
1
line: "SEr"
nd
2
line: the days of next service due day (1...400
o
days).
·
Press advance button once and the 2
and is ready for adjustment.
·
Adjust the days of next service due day to "OFF" by turning
setting knob.
·
Press advance button once to confirm setting and go back
to normal operation.
Set programming selector to RUN position.
Siemens Building Technologies / HVAC Products
.
nd
line starts flashing