FUNCTIONAL SPECIFICATIONS AC Smart BACnet
Remarks
• Point NO. 1
1. The command executed is transmitted to the A/C regardless of the status of the A/C.
2. Present_Value property will not be used if a property has never been set in the past.
• Point NO. 2
1. If there is an operation error, the Present_Value property will be set to ACTIVE regardless of
whether the A/C is in operation or not.
• Point NO. 5
1. This object supports the Intrinsic Reporting function. When the Present_Value property changes,
the corresponding Event will be transmitted if the Event has been registered.
• Point NO. 6
1. During a read operation of the Present_Value property, the Fliter Limit Sign Reset will be always
the same value as the Filter Limit Sign object.
2. Only if INACTIVE is written to the Present_Value property during a write operation, the filter sign
information resets ON signs and nothing will be executed even if ACTIVE is written.
3. This object supports the Intrinsic Reporting function. When the Present_Value property changes,
the corresponding Event will be transmitted if the Event has been registered.
• Point NO. 7
1. The Present_Value property will be set to "1: Cool" as the default value if property has never
been set in the past.
2. The air conditioner will ignore the command to an object that does not have right to select
operation mode. Therefore, the controlled/monitored system must not use this object for the air
conditioner without the right to select operation mode.
• Point NO. 11
1. The A/C will disregard the command which the object which can't select the operation mode.
Therefore, controlled/monitored system shouldn't use the object which can't select the operation
mode.
• Point NO. 12
1. Present_value property will be set to "1:Low" as the default result if the property has not been set
in the past.
• Point NO. 16
1. This object's error code descriptions should be referred to the corresponding table at the
"Reference LG original Error Code".
• Point NO. 17
1. Th is object is for vent only, and will not apply if the property has not been set in the past.
• Point NO. 18
1. This object is for vent only, and will not apply if the property has not been in the past.