10. Alarm Setpoint Adjustment

Setpoints cannot be adjusted if trip multiply is installed and active. Trip multiply is active
when the trip multiply contacts are closed.
1.
Open the front panel by loosening the two monitor retaining screws and sliding the
front panel to the right.
2.
Select the channel to be adjusted by setting either switch AA (Adjust channel A) or
AB (Adjust channel B) to the left (ON). The selected bargraph will start flashing.
3.
To adjust the Alert or Danger setpoints, press and
hold the ALERT or DANGER button on front panel and
then press the (↑) or (↓) buttons on the System
Monitor to adjust setpoint value up or down.
4.
Reset the selected channel adjust AA or AB switches
to the right (OFF).
NOTE:
The monitor responds to the previous
setpoint until the option adjust switch is turned off.
Section 10 - Alarm Setpoint Adjustment
25