Specifications - Toshiba CV-1GAU Instruction Manual

Vacuum contactors 1.5kv - 2.5kv voltage class
Table of Contents

Advertisement

SPECIFICATIONS

Table 4 – Ratings
Type Form
Rated Insulation Voltage
Rated Operation Voltage
Rated Current
Rated Frequency
Rated Insulation Level - A kV
Rated Insulation Level - Im kV
Rated Making Capacity
Rated Breaking Capacity
Rated Short Time Current kA
Operating Cycle
Method of Operation
Mechanical Endurance
Electrical Endurance
Operation Voltage
Closing Time
Opening Time
Closing Current
Holding Current
Auxiliary Switch
Total Weight
Standard
CV-1GAU
kV
kV
1.5/2.5
A
160
Hz
kA
1.6
kA
1.6
2.4 - 1s
0.96 - 30s
time/hr
NON-LATCHED
Ops.
2,500,000
Ops.
500,000
V
AC 110-240
DC 110-240
ms
55 average
ms
65 average
A
7.2/6.9 (56/60Hz, AC100V)
4.0/3.9 (56/60Hz, AC240V)
7.2/4.5 (DC100/220V)
A
0.10/0.08 (56/60Hz, AC100V)
0.10/0.09 (56/60Hz, AC240V)
0.09/0.04 (DC100/220V)
2a, 2b (Max. 4a, 4b)
kg
10.5 (23.1)
(lbs.)
(IEC/NEMA/JEM)
CV1-HAU
3.6
320
50/60
10
30
3.2
3.2
4.8 - 1s
1.92 - 30s
1200
11 (24.2)
Page 24
CV-1GAU-P2
CV1-HAU-P2
3.6
1.5/2.5
160
50/60
10
30
1.6
1.6
2.4 - 1s
4.8 - 1s
0.96 - 30s
1.92 - 30s
1200
NON-LATCHED
2,500,000
500,000
AC 110-240
DC 110-240
55 average
35 average
7.2/6.9 (56/60Hz, AC100V)
4.0/3.9 (56/60Hz, AC240V)
7.2/4.5 (DC100/220V)
0.10/0.08 (56/60Hz, AC100V)
0.10/0.09 (56/60Hz, AC240V)
0.09/0.04 (DC100/220V)
2a, 2b (Max. 4a, 4b)
10.5 (23.1)
11 (24.2)
(IEC/NEMA/JEM)
320
3.2
3.2

Advertisement

Table of Contents
loading