Installation Manual for Outdoor Unit
No. 0150525031
• Please read this manual carefully before using.
• Keep this operation manual for future reference.
Original instructions
AV08IMVEVA
AV10IMVEVA
AV12IMVEVA
AV14IMVEVA
AV16IMVEVA
AV18IMVEVA
AV20IMVEVA
AV22IMVEVA
AV24IMVEVA
AV26IMVEVA

Advertisement

loading

Summary of Contents for Haier AV08IMVEVA

  • Page 1 Installation Manual for Outdoor Unit AV08IMVEVA AV10IMVEVA AV12IMVEVA AV14IMVEVA AV16IMVEVA AV18IMVEVA AV20IMVEVA AV22IMVEVA AV24IMVEVA AV26IMVEVA No. 0150525031 • Please read this manual carefully before using. • Keep this operation manual for future reference. Original instructions...
  • Page 2: Table Of Contents

    User Manual Contents Safety ....................................1 Installation instruction ................................3 Installation procedure ..............................13 Installation procedure ..............................14 Electric wiring and the application ...........................23 Electric wiring and the application ...........................24 Failure code ..................................35 Trial operation and the performance ..........................40 MRV Ⅴ adopts "simultaneous control" type, all indoors should be heating or cooling simultaneously. To protect compressor, before startup, the unit should be electrified for over 12 hours.
  • Page 3: Safety

    Safety • If the air conditioner is transferred to the others, this manual should be tranferred together. • Before installation, please read "Safety precaution" carefully to confirm the correct installation. • The mentioned precaustion includes " WARNING" and " CAUTION". The precausion caused death or heavy injury for faulty installation will be listed in "...
  • Page 4 Safety CAUTION • Execute earthing for the unit. But the earthing wire can not be connected to the gas pipe, water pipe, lightening rod or the telephone earthing wire. Improper earthing will cause electric shock. • Don't install the unit at the place where leaks the flammable gas. Or it will cause fire. •...
  • Page 5: Installation Instruction

    Installation instruction In installation, please check specially the below items: • If the connected units quantity and the total capacity is in the allowable range? • If the refrigerant pipe length is in the limited range? • If the pipe size is proper? And if the pipe is installed horizontally? •...
  • Page 6 Installation instruction Indoor Combined The most Allow the most Gather pipe capacity Capacity recommended Total indoor Combination Type connected range indoor unit capacity(100W) indoor units number 162400 combination(18+20+20) 812~2111 168000 combination(20+20+20) 840~2184 173500 combination(20+20+22) 868~2256 179000 combination(20+22+22) 895~2327 184500 combination(22+22+22) 922~2398 191000 combination(22+22+24)
  • Page 7 Installation instruction The unit should be installed at the • The place where the water can flow • The unit is better not be installed place where the cold/hot air or fluently. at the below places, or it will cause noise will not interfere the neighbours.
  • Page 8 Installation instruction Outline and installation dimensions Fixed hole distance AV08~16IMVEVA 800mm Drain hole 750mm 980mm 70mm Exhaust duct connection position Power line outlet (According to the choice of the power line diameter size. The export, use the attached wire into the sheath) Signal line and Line protection Signal wire hole diameter Ø25...
  • Page 9 Installation instruction Outdoor unit installation Standard accessories Please check the attachment is complete, please be sure to use. definition Graphic Quantity Remarks Place position Installation Accessory bag instruction Rubber plug Signal line protection Accessory bag sheath Power line protection Accessory bag Reducing pipe Reducing pipe Accessory bag...
  • Page 10 Installation instruction Combination installation dimensions • There should be no obstacles in 2000mm above the top of outdoor unit; • Obstacles around outdoor should be less than 900mm to the bottom of unit. • When multiple modules are installed, the outdoor should be in ranked as the capacity, the larger capacity is closer to the main pipe of gather pipe.
  • Page 11 Installation instruction ˃300mm ˃200mm ˃300mm ˃1000mm 3. Wall higher than the outdoor condenser Place with air inlet hole Notes: a. Fan speed Vs at air inlet is 1.5m/s or below. b. Air outlet height HD=H-h and below 1m. ˃300mm ˃200mm ˃1000mm ˃300mm External air...
  • Page 12 Installation instruction Place without air inlet hole Notes: a. Set a 500~1000mm bracket. b. Air outlet height HD=H-h and below 1m. ˃300mm ˃300mm ˃200mm ˃1000mm External air duct 4. The outdoor machine installation should consider the impact of seasonal wind, don't let the wind directly into the unit return air, otherwise it will affect the unit defrosting and related functions 5.
  • Page 13 Installation instruction install snow cover Outlet snow cover Snowfall area, please install snow cover, see the right Inlet snow cover picture,To be unaffected by the snow, it is important to set up a high platform, which is calculated according to the maximum amount of snow in the area.
  • Page 14 Installation instruction Install air ducting There are no obstacles in the 2000mm above the outdoor unit; When there are obstacles in the outer plane, there must be a pilot channel, and the wind will be free, the wind will not beshort-circuited, and the external static pressure will be 110Pa.
  • Page 15: Installation Procedure

    19.05 is O-type, the pressure preservation will be bad, thus it must be 1/2H type and over the min. thickness. 3. The branch pipe and the gather pipe must be from Haier. 4. When installing the stop valve, refer to the relative operation instruction.
  • Page 16: Installation Procedure

    Installation procedure Pipe specification Outdoor Indoor Liquid pipe Gas pipe Liquid pipe Gas pipe Gas pipe Liquid pipe Liquid pipe pipe outdoor gather pipe the first branch pipe 1. Pipe "A" diameter (between indoor and branch pipe) (depends on indoor pipe) Indoor (x100W) Gas pipe Liquid pipe...
  • Page 17 Installation procedure 3. Pipe “c” diameter (main pipe, between outdoor gather pipe and the first branch pipe) Main pipe Enlarged main pipe Main pipe Enlarged main pipe Outdoor Outdoor capacity capacity Liquid Liquid Gas pipe Gas pipe Liquid pipe Gas pipe Gas pipe Liquid pipe pipe...
  • Page 18 Installation procedure Allowable piping length and drop between indoor and outdoor 1. Pipe length between outdoors Outdoor outdoor gather pipe 1. L1≤10m; L2≤10m; L3≤10m; L4≤10m; L5≤10m; L6≤10m; L1+L3+L5≤10m. 2. Height difference between outdoors: h≤5m. 3. The piping connecting outdoor unit must be placed horizontally or in accordance with the installation of a certain angle (level angle less than 15 degrees), connected with a concave not allowed.
  • Page 19 Installation procedure Proper installatio Wrong installation Oil return bend Compressor oil will flow into The height of the vertical the lowest unit section see schedule requirements In order to avoid damage to the pipe, the size of the return bend is referred to as the drawing. Pipe diameter Bending radius Vertical heigh...
  • Page 20 Installation procedure Allowable Pipe length and drop (m) For example Remarks value Total pipe length ≤1100 L1+L2+L3+L4+…+L24 Actual length ≤220 Outdoor to the farthest L1+L2+L3+L6+L8 indoor length Equivalent length ≤260 The outdoor unit to the first branch pipe ≤130 length (main piping) The first branch pipe to the farthest indoor ≤90 L2+L3+L6+L8...
  • Page 21 Installation procedure Pipe installation Important • Please don't let the pipe and the parts in the unit collide each other. • When connecting the pipes, close the valves fully. • Protect the pipe end against the water, impurity into the pipes (welding after being flat, or being sealed with adhesive tape).
  • Page 22 Installation procedure B. Leakage test 1. The outdoor unit has been executed the leakage test in the factory. The pipe should be executed leakage test individually and forbidden to test after connecting with stop valve. 2. Refer to the below figure to charge the nitrogen into the unit to take a test. Never use the chlorin, oxygen, flammable gas in the leakage test.
  • Page 23 Installation procedure Tighten torque as the table below: Stop valve diameter Fastening torque Fastening angle Recommended tool length (mm) (N.m) (°) (mm) Ø6.35 14~18 45~60 Ø9.52 34~42 30~45 Ø12.7 49~61 30~45 Ø15.88 68~82 15~20 Ø19.05 84~98 15~20 D. Additional refrigerant charging Charge the additional refrigerant as liquid state with the gauge.
  • Page 24 Installation procedure Heat insulation • HP gas pipe, Suction gas pipe and liquid pipe should be heat insulated separately. • The material for HP gas pipe and Suction gas pipe should endure the high temperature over 120°C. That for liquid pipe should be over 70°C.
  • Page 25: Electric Wiring And The Application

    Power Circuit Each module Model load current (mA) response sectional area of area of earthing source breaker circuit breaker time(S) power line (mm line (mm AV08IMVEVA 20.3 AV10IMVEVA 21.8 AV12IMVEVA 23.3 AV14IMVEVA 27.7 3N~, AV16IMVEVA 32.4 30mA, below0.1s 380V, AV18IMVEVA 36.1...
  • Page 26: Electric Wiring And The Application

    Electric wiring and the application 2. If the power cord length is greater than 20m, please increase the cable cross-sectional area, so as to avoid overload caused by the accident. 3. When the voltage drop at the power supply line exceeds 2%, increase the wire diameter appropriately. 4.
  • Page 27 Electric wiring and the application Power line installation instructions Note: When connecting the power cord, please be sure to set aside enough length in the outdoor, which is convenient for turning over the electrical box. After the maintenance, remove the 5 fixing screws, the When connecting the power cord, please be sure electric appliance box body is lifted up slightly, and the box to set aside enough length in the outdoor, which is...
  • Page 28 Electric wiring and the application When the outdoor unit is combined, only the host machine is installed IGU09, and the sub machine is connected with the main machine through the communication terminal of the A/B/C. Indoor 1 Indoor 2 Indoor 3 Indoor 4 Indoor n CN34...
  • Page 29 Electric wiring and the application Internal layout of electric appliance box For example Compressor Fan drive drive module module (external or built-in motor) Capacitor plate Filter board Power Communication Main control board Reactance terminal terminal Outdoor dip switch introduction Identification: •...
  • Page 30 Electric wiring and the application ① BM1 introduction begin to search outdoor outdoor searching BM1_1 after startup stop searching outdoor and lock the quantity begin to search indoor indoor searching BM1_2 after startup stop searching indoor and lock the quantity allow(must be electrified for 6 hours) start up after pre- BM1_3...
  • Page 31 Electric wiring and the application ③ BM3 introduction BM3_1 BM3_2 BM3_3 Outdoor BM3_1 The outdoor Normal Outdoor machine model BM3_2 machine is Update use BM3_3 effective Low temperature heating BM3_5 BM3_6 BM3_7 BM3_8 Outdoor horse 10HP 12HP BM3_5 14HP BM3_6 16HP Outdoor horse power BM3_7...
  • Page 32 Electric wiring and the application Outdoor machine digital tube display settings The contents of the display are defined as follows: • Key parts: long press the left START (SW5) control to enter, short press above UP (SW4) data increase, short press down DOWN (SW7) data reduction, long press the right STOP (SW6) control exit •...
  • Page 33 Electric wiring and the application function Digital tube LD1 ~ 4 display (1) press START (SW5) for 2 seconds, to enter the instruction set state, flashing display instructions. Forced indoor mechanism (2) according to UP (SW4) or DOWN (SW7) () adjustment instructions (COOL/ 14(E)...
  • Page 34 Electric wiring and the application function Digital tube LD1 ~ 4 display Outdoor unit LEVa1 open degree 0---470pluse Press START (SW5) for 2 seconds, 1111, enter the Outdoor unit LEVa2 open degree set state: flashing, press UP (SW4) valve fully open, according to DOWN (SW7) 2min after the valve is fully Outdoor unit LEVb open degree closed;...
  • Page 35 Electric wiring and the application function Digital tube LD1 ~ 4 display Outdoor 14(E) 15(F) Frequency converter INV1 module temperature Unit: degree unit address 15(F) 15(F) Frequency converter INV2 module temperature Unit: degree ③ System status display and control (host) function Digital tube LD1 ~ 4 display Refrigerant type...
  • Page 36 Electric wiring and the application Control function Digital tube LD1 ~ 4 display range 0- machine automatic control according to the In the same machine drive group number, all within the machine with 15(F) off control selection 1- drive, 2- all in each machine control, drive off with ban Selection of low temperature 0- within the machine automatic control, 15(F)...
  • Page 37: Failure Code

    Failure code Failure code description: (failure code of the whole system is showed as 8 bits, so totally 256 codes. Indoor failure code should be judged by the table and the unit number) • Outdoor failure code exists in EEPROM, in which 5 failure codes can be kept. •...
  • Page 38 Failure code Digital tube indication Failure code definition Failure description Remarks on master unit Oil temp.too high 27-0 protection Toil ≧ 120℃ continuous 2sec exceeds the set value after Once shutdown alarm; the alarm condition after stopping the oil (Toil1) confirmation temperature below 10 degrees, automatic recovery after 2min50s.
  • Page 39 Failure code Digital tube indication Failure code definition Failure description Remarks on master unit Discharging temp. 43-0 sensor Tdi too low In normal operation,If Td < CT+10℃ for continuous 5 minutes, Once protection the unit stops and alarms.2 minutes and 50 seconds later,resume confirmation Discharging temp.
  • Page 40 Failure code Digital tube indication Failure code definition Failure description Remarks on master unit Module rectifier side software transient overcurrent Module rectifier side current detection circuit anomaly Module hardware overcurrent In the process of starting or running, the rotor position can not Compressor out of step be detected for 6 times in a row, and the INV control board is automatically restored after stopping 5S...
  • Page 41 Failure code In the case of no fault, if the system does not meet the start-up conditions, the host digital display standby code: Indoor machine capacity beyond the outdoor Indoor machine capacity beyond the outdoor 555.0 machine capacity of 150% or less than 50%, machine capacity of 150% or less than 50%, standby standby system system...
  • Page 42: Trial Operation And The Performance

    Trial operation and the performance 5-minute delay function • If starting up the unit after being powered off, the compressor will run about 5 minutes later against being damaged. Cooling/heating operation • Indoor units can be controlled individually, but cannot run in cool and heat mode at the same time. If the cool mode and the heat mode are existing simultaneously, the unit set latter will be standby, and the unit set earlier will run normally.
  • Page 43 Trial operation and the performance Trial operation • Before trial operation: Before being electrified, measure the resistor between power terminal block (live wire and neutral wire) and the earthed point with a multimeter, and check if it is over 1MΩ. If not, the unit can not operate. To protect compressor, electrify the outdoor unit for at least 12 hours before the unit runs.If the crankcase heater is not electrified for 6 hours, the compressor will not work.
  • Page 44 Qingdao Haier Air Conditioner Electric Co.,Ltd. Haier Industrial Park,Qianwangang Road,Eco-Tech Development Zone,Qingdao 266555, Shandong,P.R.C.