Disturbance Recorder - Hitachi ABB RELION REB500 Communication Protocol Manual

Distributed busbar protection
Table of Contents

Advertisement

1MRK 511 451-UEN Rev. C
Table 12:
INF
<19>
4.3

Disturbance recorder

Disturbance data are uploaded and displayed in accordance with the IEC recommendation
with the following exceptions:
REB500 supports a maximum of 15 records per Bay Unit, but only the first (oldest) eight in
the queue can be displayed in accordance with the recommendation.
Of the records that are displayed, only the oldest can be deleted or uploaded. This is
determined by the REB500 principle.
The time stamp invalid bit (IV) in a disturbance record is always set, because the CIM
module is unaware of the synchronization status at the instant of the record.
Creating an export file
HMI500 provides facility for exporting the IEC 60870-5-103 communication data contained in
the system database in the form of a text file (export file). To do this, select Tools/Export SCS
data and IEC 60870-5-103 IBB and then click on the Export button.
The application creates a text file (export file) iec103exp.lst, which contains all the information
required.
The file has the following structure:
1.
Disturbance recorder signal configuration
2.
IEC 60870-5-103 events
The columns are separated by a semicolon (;). The following is an example of an export file
generated by HMI500:
--------------------------------------------------------------------------
------------------------
IEC 60870-5-103 Disturbance Recorder signals
--------------------------------------------------------------------------
------------------------
CAA;ABB ref.; Feeder; Station number; Signal ID; Signal text
0;CU;-;Null;Null;Null
2;BU2;BU2;2;1;Trip
2;BU2;BU2;2;2;In service
--------------------------------------------------------------------------
------------------------
IEC 60870-5-103 events and private Information Object Identifier settings
--------------------------------------------------------------------------
------------------------
CAA;ABB ref.; Feeder; Signal text; IEC FUN;IEC INF
0;CU;BU2;41810_In service;254;18
2;BU1;BU1;23310_BFP trip t2;254;85
2;BU1;BU1;221105_I0INV Trip Si;160;67
2;BU1;BU1;211880_DIST Com Send.2;128;76
Distributed busbar protection REB500
Communication protocol manual IEC 60870-5-103
Commands in control direction
Description
LED reset
The upload of disturbance data from the central unit is not possible via IEC
60870-5-103.
© 2019 - 2020 Hitachi Power Grids. All rights reserved
TYPE
COT
FUN
20
20
254
Section 4
IEC 60870-5-103
CAA
Central Unit
GUID-442CE5CB-AD4B-428F-9921-15E145294B02 v3
15