ABB ACS580MV Commissioning Manual page 116

200kw to 6300 kw,3.3kv to 11 kv
Hide thumbs Also See for ACS580MV:
Table of Contents

Advertisement

116 Option
Marshalling PLC
Setting
parameter
Par.10 MSS close
3s
time limit
(example)
Par.11 MB open
3s
time limit
(example)
Par.12 MSS open
3s
time limit
(example)
Par.13 MSS close
5s
waiting time
(example)
Par.14 Motor grid
External
configure
(example)
Par.23 PLC IO
Done
refresh
(example)
Par.50 Motor 1
UserSet1
user set
(example)
Par.51 Motor 1
External
grid selection
(example)
Par.52 MB1 open
Disable
DOL enable
(example)
Par.53 MB1 close
Disable
DOL enable
(example)
Set for motor 2 to
motor 8
Connect the Marshalling PLC and PC with Ethernet cable.
Open
http://192.168.0.10/webvisu.htm
Input service level pass code in Par.24.
Description
Define maximum operating time for closing MSS
Define maximum operating time for opening MB
Define maximum operating time for opening MSS
Define the MSS operating waiting time, after switching off the motor.
Two grids are supported. This parameter defines the grid selection
command source. External means it's from DI (X106: 1, 2).
Parameter means it's from Motor1 grid selection... Motor8 grid
selection.
In case PLC reports
F002 PLC IO configuration
refresh PLC configuration to match actual IO modules.
After refreshing, PLC will reboot and configure correct
hardware.
This parameter will be displayed only if PLC has IO
configuration fault.
This parameter selects the user set for this motor.
Two types of motors are supported and user set is used to select the
corresponding motor data. The command is from marshalling PLC to
BCU DI5, to select user set. Every time after Motor group 1...8
selection is set, marshalling PLC will select corresponding use set.
Detailed steps:
1. Using motor data 1 for commissioning.
2. Set 96.11 User set save/load to Save to set 1. After saving is
finished, it will change to No action.
3. Set motor data 2 (99.06...99.11).
4. Set 96.11 User set save/load to Save to set 2. After saving is
finished, it will change to No action.
5. Set 96.12 User set I/O mode in1 to DI5, 96.11 User set
save/load to User set I/O mode. 96.10 User set status will show
the user set selected by marshalling PLC.
This parameter selects the grid for this motor. It works only when Par.
14 Motor grid configure is Parameter.
Parameter selects if MB1 open command is set if the direct online
(DOL) signal is removed (1→0).
Parameter selects if MB1 close command is set if the direct online
(DOL) signal is set (0 →1).
if SBM>=0002
by Internet Explorer to show Web visualization.
fault,