5. Parts included list
•
This unit includes the following parts. Please check.
Model
P72
P96
P120
P144
6. Space required for unit installation and operation
1 In case of single installation
•
Secure enough space around the unit as shown in the fi gure below.
[Fig. 6.0.1]
(1) If the distance is 300 mm [11-13/16 in] or more between the rear side
and the wall
<A> Top view
300*
[11-13/16]
A
450*
[17-23/32]
15*
15*
[19/32]
[19/32]
(2) If the distance is 100 mm [3-15/16 in] or more between the rear side and
the wall
<A> Top view
100*
[3-15/16]
A
450*
[17-23/32]
50*
50*
[1-31/32]
[1-31/32]
(3) If the wall height (H) of the front, rear or side exceeds the wall height
restriction
<B> Side view
B
A
•
When the height of the walls on the front, back or on the sides <H> exceeds
the wall height limit as defi ned here, add the height that exceeds the height
limit <h> to the fi gures that are marked with an asterisk (*).
<Wall height limit> Front: Up to the unit height
Back: Up to 500 mm [19-11/16 in] from the unit bottom
Side: Up to the unit height
Adapter
<Check joint>
2 pcs.
2 pcs.
2 pcs.
2 pcs.
(Unit: mm [in])
(Unit: mm [in])
(Unit: mm [in])
(4) If there are obstacles at the upper part of the unit
<C> When there is little space up to an obstruction
45°
240
[9-15/32]
50
[1-31/32]
A
B
Front
Unit height
C
D
Back
Air outlet guide (fi eld-supplied)
(Unit: mm [in])
1000
[39-3/8]
D
A
C
5