NOTE:
When this unit is set to sub system controller by No.2 function select, interlocked operation settings
cannot be adjusted. However monitoring of the contents of the interlocked operation settings is possible.
6Used the numeric keypad switch to set the address of the indoor unit that
operates with displayed interlocked OA processing unit or LOSSNAY.
<Operation example>
When the indoor unit which address is 012.
1) Input "0"
0
2) Input "1"
01
3) Input "2"
012
4) Press the
switch 012
* It is also possible just enter "1" "2".
<When the input is incorrect>
Before pressing
switch, move the cursor to the address to be deleted and press the
switch to delete these addresses.
DEL.
7Set all the indoor units that operate with displayed interlocked OA pro-
cessing unit or LOSSNAY.
8Repeat operation 5 to 7 to set the indoor units of all interlocked opera-
tion units managed by this controller.
9When all settings are completed, press the
Initial setting screen is displayed.
This ends the interlocked operation setting.
When the interlocked operation settings are performed, refer to section
"5-5 Interlocked operation setting".
When the group name settings are performed, refer to section "5-6 group
name setting".
When the user setting are performed, refer to section "5-7 user setting".
Simultaneously press the
screen for 2 seconds to complete user operation. After the initial setting
processing is completed (The initial setting screen will be displayed), refer
to section "4. User operation (page 10)" and perform user operation.