Advertisement

Path
Choose System Settings >
Device Management and
click Add Device. The
parameters for adding
devices are displayed.
2. Click Test Connect.
3.8
Commissioning the Smoke DSetector
1. Set smoke detector parameters.
a) Log in to the ECC800-Pro WebUI as an administrator.
b) Choose System Settings > Signal Name Modify. The Batch Signal Configuration tab
page is displayed.
c) Set Device type to ECC800, set Device name to ECC800, and click OK.
d) On the query result tab page, set the new signal name of AI/DI_1 to Smoke and click
Submit.
e) Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_1 Port Settings.
f) Set Smoke sensor to Enable and click Submit.
g) Confirm that Smoke sensor type is automatically identified as Smoke sensor.
2. Check the monitoring functions of smoke sensor.
Check Method
Simulate a smoky
environment under
the smoke detector.
3.9
Commissioning the Electrode Water Sensor
1. Set water sensor parameters.
a) Log in to the ECC800-Pro WebUI as an administrator.
b) Choose System Settings > Signal Name Modify. The Batch Signal Configuration tab
page is displayed.
c) Set Device type to ECC800, set Device name to ECC800, and click OK.
d) On the query result tab page, set the new signal name of AI/DI_2 to Leak and click
Submit.
e) Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_2 Port Settings.
f) Set Leak sensor to Enable and click Submit.
g) Set Leak sensor type to Leak sensor(Electroc) and click Submit.
Parameter
Device attribute
Device attribute
Connect To
Communications
Port
Device Address
Normal Connection Status
Smoke DI alarm is displayed
on the active alarm page of
the app or WebUI.
17
Setting
Select UPS from the drop-down list box.
Select UPS2000G-L from the drop-down list box.
Select ECC800 from the drop-down list box.
Select COM4 from the drop-down list box.
The setting example indicates that the
UPS2000G is connected to the COM4 port on
the ECC800-Pro.
During actual configuration, set the device
address for the UPS2000G-L based on the actual
situation.
Alarm Clearance Method
Disconnect the smoke detector
cable and then reconnect it to
clear the alarm.