Initial Configuration Parameters of the Electric Heater Temperature Controller for Air Inlet Windows
Category
Specified value
SET
Hy
Temperature difference
AC
Anti-frequent–startup delay
Adjustment parameters
Probe error, compressor running time
Cy
Cn
Probe error, compressor stop time
Control direction (cooling cL, heating Ht)
CH
Defrosting time interval
id
Defrosting parameters
Md
Maximum allowed defrosting time
Display the temperature during the defrosting period (rt = actual warehouse temperature; it =
dF
temperature before defrosting starts; St = specified value; dF = abbreviation of defrosting
Item
Default Value
Value Range
–55°C to 99°C
N/A
2.0°C
0.1°C to 25°C
1
0–50 min
15
0–99 min
30
0–99 min
cL
cL–Ht
6
0–99 h
30
0–99 min
it
rt – it – St – dF
Factory Setting
Remarks
25°C
N/A
20°C
N/A
1
N/A
0
N/A
0
N/A
Ht
N/A
0
N/A
0
N/A
it
N/A