Certification
6.2 EMC and Environmental Type Tests
61000-4-8
61000-4-11
61000-4-12
61000-4-16
61000-4-17
61000-4-29
IEC 60255-5
38
Test
IEC
Magnetic Field
IEC
Voltage Dips and Interrupts
IEC
Damped Oscillatory
IEC
Mains Frequency Voltage
IEC
Ripple on DC Power Supply
IEC
Voltage Dips and Interrupts
Dielectric Strength
HV Impulse
Description
DC Power
Ports
AC Power
Ports
Earth
Ground Ports
Enclosure
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
DC Power
Ports
DC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Test Levels
10 V
10 V
10 V
40 A/m Continuous
1000 A/m for 1 s
100% for 5 Periods
100% for 50 Periods
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
30 V Continuous
300 V for 1 s
30 V Continuous
300 V for 1 s
10%
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
2 kV (Failsafe Relay Output)
1.5 kV
2 kV
5 kV (Failsafe Relay Output)
5 kV
5 kV
Installation Manual, 04/2021, C79000-G8976-1350-07
Severity
Levels
3
3
3
 
 
3
3
3
4
4
3
 
 
 
 
 
 
 
RUGGEDCOM RS900F