Siemens SIMATIC Manual page 54

Automation system
Hide thumbs Also See for SIMATIC:

Advertisement

2nd step: Assigning parameters
Step
Action
1
Open your project in SIMATIC Manager.
2
In your project, call the configuration table HW Config.
3
Double–click on the "PtP" submodule.
4
Select the "ASCII" protocol and enter the default settings in the parameter masks with a
click on OK:
S
9600 bits/s, 8 data bits, 1 stop bit, even parity.
5
Confirm your entries with OK.
6
Save your project configuration with Station >
Save and compile.
7
While the CPU is in STOP state, download this
configuration via PLC > Load to module....
8
Close HW Config with Station > Close.
4
Result
A split window opens, showing your pro-
ject name in the header.
The "PtP properties" dialog opens.
The "PtP properties" dialog is closed.
Your changes are now stored in your
project.
Data are downloaded from the PG to
your CPU.
You are returned to SIMATIC Manager.
Automation System S7-300, Getting Started – PtP