Mitsubishi Electric LGH-F300RVX-E Handbook page 29

Lossnay energy recovery ventilator
Hide thumbs Also See for LGH-F300RVX-E:
Table of Contents

Advertisement

Error
LED1
LED2
Symptom
code
(Green)
(Red)
4116
2
Abnormal
blinks
rotation of the
exhaust fan
motor
(in the lower
unit for LGH-
F1200RVX-E)
(Centrifugal
fan does not
work, insuf-
ficient motor
speed, ex-
cessive motor
speed, or
rotation de-
tected when
operation is
stopped)
Cause
Faulty connection of the exhaust fan
motor connector (CN9) on the power
circuit board
Faulty connection of the connectors
(CN18 - CN118 and CN19 - CN119)
between the control circuit board and
power circuit board
The model selection switch (SW6) is
not set correctly.
The temperature around the product
is high.
The motor and centrifugal fan are not
fixed securely.
Deformed centrifugal fan
Foreign objects around the centrifu-
gal fan
Fan motor failure
Circuit board failure
─ 29 ─
Corrective action
Check the connector (CN9) connec-
tion.
Check the connector connections
(CN18 - CN118 and CN19 - CN119).
Make the SW6 setting appropriate
for the model.
(See chapter 8. (8) Setting status
record (page 48).)
Use the product at a temperature of
104°F (40°C) or lower.
Check the installation state of the
motor and centrifugal fan, and fix
them securely.
Replace the centrifugal fan.
Check the air course and around
the centrifugal fan, and remove any
foreign matter.
Check the resistance between the
motor leads.
(See (6) Motor resistance table
(page 36).)
If the measured value is significantly
different from the values specified in
the table, replace the fan motor.
Replace the circuit board.