Mitsubishi Electric LAHN-1 Installation Manual page 11

Low ambient hoods
Hide thumbs Also See for LAHN-1:

Advertisement

9. Wiring diagram
green
Ground
orange
white
black
red
red
Terminal strip
Outdoor Unit Control Board
common (blk)
1 amp fuse
230/460v (wh)
208v (or)
M
F
Insert the black plug into the CNAC2 connection
on the board. Connect the white wire (male
connector) to the wire that corresponds to the
F
outdoor unit supply voltage as shown below
208 volt = orange wire (female connector)
230/460 volt = white wire (female connector)
red
F
M
red
M
F
Disconnect white plug with four wires from
male connector from the low ambient kit onto
green
the CN505 connection. Connect the white
plug with four wires onto the spare connection.
© 2019 Mitsubishi Electric US, Inc.
LAHN-1/LAHN-3 Wiring Diagram
Control Box Mounted on Hood
orange
white
4
black
red
5
240 volt ac
NC Relay
red
1
3
CNAC2 Connection
black
CNAC2
white
move and secure cap to unused wire
CN505 Connection
To reversing valve 21S4a
yellow
6
5
4
3
2
1
the CN505 connection. Plug the white
40 VA
Transformer
208v
red
230V
R
24 V
Com
C
blue
Circuit Board
+
Sensor
2-10VDC
-
C
-
24v
+
10K ohm thermistor
Low Ambient Hood
Part Number
Supply Voltage
Amps
Fuse Size
For Use with Modular N-Generation
Y-Series Outdoor Units Only
Serial Number
Date of Manufacture
Initials
Manufactured for Mitsubishi Electric US, Inc.
Damper Actuator
black
Black
(1)
Common
red
Red
(2)
+ Hot
white
White
(3)
2-10VDC
Orange
(5)
Y=0
Y=0
Factory switch positions
LAHN-1/LAHN-3
208/230V, 1-phase, 60Hz
0.20
1 amp
11