9 TROUBLE SHOOTING
Error
Error name
code
Network
0627h
communication route
error
Tag sampling interval
0628h
setting error
Update-before-logging
0629h
setting error
062Ah
Data write setting error
062Bh
File name setting error
Component setting
062Ch
error
No CPU specification
062Dh
error
Data type incorrect
062Eh
error
Excessive number of
062Fh
characters error
Decimal/Exponential
0630h
form setting error
0631h
Operation setting error
9 - 33
Error definition
The network No., start I/O
address, or station No. set in
"Network communication route" of
the access target CPU setting is
outside the range.
Invalid setting was made in
"Sampling Interval" of the tag
setting.
Invalid setting was made in
"Update before logging" of the tag
setting, or the tag setting file is
destroyed.
Invalid setting was made in "Data
write" of the tag setting, or the tag
setting file is destroyed.
Invalid setting was made in "File
name" of the logging setting.
Invalid setting was made in
"Component setting" of the tag
setting, or the tag setting file is
destroyed.
The access target CPU specified
in the component setting does not
exist, or the access target CPU
has been deleted.
The device specified in the
component setting is not
consistent with the data type. (A
device other than a bit device was
specified as a bit device or vice
versa.)
The number of characters
specified in the component setting
is outside the range.
Invalid setting was made in
"Display form" of the component
setting.
Invalid setting was made in
"Operator/Operand" of the
component setting.
(From the previous page)
Corrective action
 Check the access target CPU
setting. (Refer to Section 4.6.7)
 Check the tag setting.
(Refer to Section 6.3.3)
 After initializing the module (refer
to Section 4.13), perform the tag
setting (refer to Section 6.3.3)
again.
 After initializing the module (refer
to Section 4.13), perform the tag
setting (refer to Section 6.3.3)
again.
 Check the logging setting.
(Refer to Section 6.4.4)
 After initializing the module (refer
to Section 4.13), perform the tag
setting (refer to Section 6.3.3)
again.
 Specify the existing access target
CPU.
 Check the component setting.
(Refer to Section 6.3.3)
 Check the component setting.
(Refer to Section 6.3.3)
 Check the component setting.
(Refer to Section 6.3.3)
 Check the component setting.
(Refer to Section 6.3.3)
(Continued on the next page)
MELSEC-Q
Error type
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
9 - 33