Control item
On Off Setup
On Off State
Alarm Signal
Error Code
Operational Mode Setup
Operational Mode State
Fan Speed Setup
Fan Speed State
Room Temp
[Water Temp]
Set Temp
[Set Water Temp]
Filter Sign
[Circulating Water Exchange Sign]
Filter Sign Reset
[Circulating Water Exchange Sign Reset]
Prohibition On Off
Prohibition Mode
Prohibition Filter Sign Reset
[Prohibition Circulating Water Exchange Sign
Reset]
Prohibition Set Temperature
M-NET Communication State
System Forced Off
Air Direction Setup
Air Direction State
Set Temp Cool
Set Temp Heat
Set Temp Auto
Set High Limit Setback Temp
Set Low Limit Setback Temp
Ventilation Mode Setup
Ventilation Mode State
Air To Water Mode Setup
Air To Water Mode State
Expansion Controller Communication State
: Controllable
 : Not controllable
*1: Outdoor unit errors will be detected as the errors of the entire groups that IC, KIC, AIC, LC, and FU belong to, to which the
outdoor units are connected.
SC and RC errors will not be treated as BAC-HD150 errors.
*2: The settable temperature ranges are as follows.
(The following tables show only the representative ranges. The settable range varies with the models.)
*3: Includes the FU (OA processing units) that are configured in the group but not interlocked with the indoor units.
*4: In the "ON/OFF", "Mode", "Set temp" prohibit functions, only "ON/OFF" prohibit function can be used with K-control indoor
units. "Mode" or "Set temp" prohibit functions synchronize with the state of "ON/Off " prohibit function.
*5: K-control indoor unit does not support "Filter Sign Reset" prohibit function.
*6: Not available depending on the type of units that are connected.
*7: Inside the brackets indicates control item for BU or AU group. (Refer to section 1.2 Restrictions/Cautions.)
Instance
Object type
number
BO
xxxx01
BI
xxxx02
BI
xxxx03
MI
xxxx04
MO
xxxx05
MI
xxxx06
MO
xxxx07
MI
xxxx08
AI
xxxx09
AV
xxxx10
BI
xxxx11
BV
xxxx12
BV
xxxx13
BV
xxxx14
BV
xxxx15
BV
xxxx16
BI
xxxx20
xxxx21
BV
999921
MO
xxxx22
MI
xxxx23
AV
xxxx24
AV
xxxx25
AV
xxxx26
AV
xxxx27
AV
xxxx28
MO
xxxx35
MI
xxxx36
MO
xxxx37
MI
xxxx38
BI
xx9981
- 13 -
Model group
IC Group *3
LC Group
Note
BU.AU
Group
*1
*7
*2, *7
*7
*7
*4
*4
*5, *7
*4
*6
*6