CHAPTER 8
This section describes the transmission cycle time and transmission delay time of AnyWire DB A20.
8.1

Transmission Cycle Time

The transmission cycle time is the time required for the master module and all the slave modules to update I/O data.
8.1.1

Transmission cycle time of the master module

The transmission cycle time of the master module is listed in the table below.
Maximum transmission distance (total length)
Number of
transmission
points setting
56
TRANSMISSION TIME
Transmission clock
64 points (32 input points/32 output points)
128 points (64 input points/64 output points)
256 points (128 input points/128 output points)
384 points (192 input points/192 output points)
512 points (256 input points/256 output points)
640 points (320 input points/320 output points)
768 points (384 input points/384 output points)
896 points (448 input points/448 output points)
1024 points (512 input points/512 output points)
2048 points (1024 input points/1024 output points)
125kHz
31.3kHz
50m
200m
0.42ms
1.7ms
0.7ms
2.7ms
1.2ms
4.8ms
1.7ms
6.8ms
2.2ms
8.9ms
2.7ms
10.9ms
3.2ms
13.0ms
3.8ms
15.0ms
4.3ms
17.1ms
8.4ms
33.4ms
133.8ms
7.8kHz
2kHz
1km
3km
6.8ms
24.8ms
10.9ms
40.7ms
19.1ms
72.4ms
27.3ms
104.2ms
35.5ms
135.9ms
43.6ms
167.6ms
51.8ms
199.4ms
60.0ms
231.1ms
68.2ms
262.9ms
516.8ms