Huawei FusionCol8000-E240 User Manual page 119

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Context
The parameters in this section are for reference only. Set practical parameter
values as required.
Procedure
Step 1 On the home screen, tap
Settings screen.
Figure 6-5 Teamwork setting
Step 2 Set teamwork parameters.
All teamwork control parameters can be set on the master smart cooling product.
Only Teamwork group No., Smart cooling product address, Enable teamwork
CAN resistor, Teamwork function and Networking mode can be set on slave
smart cooling products. Other parameters of the slave units will be modified by
the master unit synchronously.
Table 6-5 Teamwork setting
Parameter
Teamwork
group No.
System
address
Issue 02 (2021-04-15)
> Teamwork Settings to enter the Teamwork
Description
The number of the teamwork
group. This parameter should be
the same for all units in the same
teamwork group.
Smart cooling product addresses
should be different from each
other.
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Setting Rule
Set the assigned teamwork
group number.
Set the planned teamwork
unit address.
110