Honeywell Notifier IDR-2P User Manual page 23

Table of Contents

Advertisement

IDR-6A repeater (graphics display)
LCD CONTRAST ADJUSTMENT
Set keyswitch to right, press and hold
RESET momentarily. The LCD contrast cycles.
Press
when the contrast is satisfactory, then
use
and
to fine-tune. Press
Contrast can also be adjusted during Lamp Test
(see Section 4.5.1).
2A
OR (ID50 REPEATER ONLY)
6A
TURN KEYSWITCH WHEN THE
DISPLAY IS AS SHOWN ABOVE
IDR-2P, -2A & -6A Repeaters User Manual
then press
when finished.
19
PUSHBUTTONS (IDR-6A)
Silences repeater and panel buzzers
(locally and across the network), and
accepts an alarm.
If any delays are active, first operation
ends the delays, second operation
sounds all sounders configured for
Evacuate. If no delays are active, first
operation performs Evacuate.
Stops and restarts the sounders.
Steps through the tabbed displays.
Displays fire alarm information. If there
are fire alarms in more than one zone,
steps through these zones.
Restores normal operating status when
all alarm conditions have been removed.
KEYSWITCH (IDR-2A, -6A)
Setting the keyswitch to the right selects
access level 2. Setting it to the centre
de-selects access level 2. The procedures
given in Sections 4.3 onwards require access
level 2, unless stated otherwise.
997-411-000-9, Issue 9
March 2008