ECC800 Data Center Controller
User Manual
5.1 Setting the Date and Time
Procedure
Step 1 Choose System Settings > Time Settings.
Step 2 Set the time zone, date, and time, and click Submit.
Step 3 (Optional) If the NTP server is used for time synchronization, select NTP Server Sync, set
NTP Primary Server IP, NTP Backup Server IP, Port Number, and Sync Interval (Min),
and click Submit.
----End
5.2 Checking the System Type and Setting the Smart
Module Name
Context
Procedure
Step 1 Choose System Settings > Smart Module Settings, and check whether System Type is
consistent with the type of the smart module.
(Optional) If the system type is inconsistent with the type of the smart module, perform the
following operations. The system type FusionModule2000 is used as an example.
Issue 07 (2020-03-16)
5
System type: FusionModule500, FusionModule800, FusionModule1000A,
FusionModule1000B, FusionModule2000, and FusionModule5000 can be selected based
on the actual project configuration.
Site ID: Alarms of devices under monitoring in the site are sent to the specified mobile
phone numbers of maintenance engineers by SMS. After Smart module name is
changed, the new site ID will be displayed in the short message content (for example,
XXX device communication interruption) so that maintenance engineers will know the
site where the fault has occurred.
Copyright © Huawei Technologies Co., Ltd.
Power-On Commissioning
5 Power-On Commissioning
85