When an event or error occurs, the S10mini uses the CPU module's indicator to display a
message as indicated in the Table below.
The S10V, on the other hand, collects error information, but does not indicate any error on the
LPU module. You can view collected error information with "Error log" of the "Basic tool."
For details, refer to "S10V USER'S MANUAL BASIC MODULE (manual number
SVE-1-100)."

Table 6-2 CPU Module Error Indications and Remedies (1)

CPU module
No.
indication
(S10mini)
1
CPL▲ ROM
2
CPL▲ SSP
3
CPL▲ WDT
4
CPL▲ RAM
5
CPL▲ PTY
0x1480 (MAIN)
6
EX8■ PTY
0x1480 (SUB)
7
CPL▲NONG
8
CPL▲ GNG
Either the ▲ mark or ■ mark appears to indicate whether the main module or sub-module is
affected. (When the S10V is used, the tool system gives this type of indication.)
Error code
(S10V)
ROM checksum error:
0x0004
An error occurred in the ROM.
Stack fence over error:
0x0020
A stack fence over error occurred.
WDT error:
0x0002
A watchdog timer timeout error
occurred
RAM check error:
0x0008
An abnormality occurred in the system
program
RAM parity error:
0x0010
A parity error occurred in the RAM.
Optional module memory parity error:
A parity error occurred the CPU or
personal computer attempted to read
the RAM in the CPU link module.
The "Module" field of the S10V error
log information reads "LPU." The
other error indications are either "CPU
link (main)" or "CPU link (sub)."
CPU number switch setting error:
A module having the same CPU
0x00C0
number as this module exists on the
CPU link line.
G-register area duplication error:
The G-register area transmitted by this
0x0040
module coincides with the received G-
register area.
MAIN/SUB selector switch
"0" (MAIN)
"1" (SUB)
Error description
M
S
6-8
Action
• Hold the CPU or LPU RESET
switch in the ON position for a
period of longer than one second
and then release it.
• If the indication does not go off,
replace the CPU link module
because it is defective.
Note the CPU number selector
switch on the CPU link module
connected to the CPU link line.
Change the switch setting so that no
CPU number is duplicated.
Note the preselected number of
transfer words for the CPU link
module connected to the CPU link
line. Change the setting so as to
avoid a duplication error
0
1