Selecting The Installation Location - Panasonic S-250WX2E5 Manual

Ghp chiller system
Hide thumbs Also See for S-250WX2E5:
Table of Contents

Advertisement

1. ATTACHMENT
Attached documents
• Procedures and Technical Points for System Installation(Chillers)
• Procedures and Technical Points for Electrical Wiring Work(Chillers)
• Instruction Manual
Concerning anchor bolts
• For anchor bolts, use M10.
• Anchor bolts shall be procured locally.

2. SELECTING THE INSTALLATION LOCATION

CAUTION
1. Secure the space stipulated for inspection and maintenance work (Fig. 2). Inadequate space for
such work can create the threat of injuries due to falls from the installation site.
2. When installing the water heat exchanger unit on a roof or other elevated location, place permanent
ladders, railings or other aids in passageways to prevent worker falls, as well as fences, railing and
other aids around the unit itself.
3. Install the unit in a location facilitating easy water draining. Defective work in this category can result
in water leakage, water damage to household effects and other problems.
• Keep indoor drain pipe sections as short as possible.
• Insulate all indoor drain pipe sections.
• Adopt measures to ensure that drain water causes no problems for neighboring homes or other parties.
4. Always use a level to confi rm the horizontal level.
If it is not fl at, water leakage may occur.
Anchorbolts:M10
Fig.1 Anchor bolts
1. Avoid installations in locations where machines emitting high frequencies are present.
2. When hoisting up the water heat exchanger unit for installation site delivery:
• Attach ropes to the unit base hoisting fi xtures at 4 locations, and raise up the unit.
• When attaching ropes, use wooden splints or other aids to prevent scratching or deformation to
the facing or other damage.
• When hoisting by crane, keep the crane hook at least 1 meter from the unit.
CAUTION
• When carrying in the unit, do not allow it to tip over. Damage to the machinery can cause
subsequent breakdowns.
Over 50mm
1014mm
Wooden splints
Fig.2
Refrigerant
tubing side
Ropes
Fig.3
4
Over 600 mm
Over 1m

Advertisement

Table of Contents
loading

This manual is also suitable for:

S-500wx2e5S-710wx2e5

Table of Contents