Huawei New Main Way 2.0 User Manual page 52

Table of Contents

Advertisement

New Main Way 2.0
User Manual
2.
Step 2 Set parameters for power distribution units on the ECC800-Pro WebUI.
1.
2.
3.
Issue 05 (2020-10-15)
Path
Set the parameters for other general input units in the same way or by
synchronizing parameters.
Path: Maintenance > Parameter Sync
(Optional) To modify the branch signal name of the power distribution unit,
choose System Settings > Signal Name Modify and access the Batch Signal
Configuration to modify the name, and then tap Submit.
The following is an example of how to display two branches for power
distribution unit 1.
Choose Monitoring > Power Distribution > General Input Unit > Power
Distribution Unit > Display Configuration, select Branch Information
Display corresponding to QF1 and QF2, and then tap Submit.
Configure the power distribution settings for power distribution unit 1.
Table 4-2 Power distribution settings for a power distribution unit
Path
Parameter Name
Monitoring >
QF1 Rated current (L1)
Power
(This parameter is not
Distribution
displayed for some
> General
distribution units.)
Input Unit1
QF2 Rated current (L2)
> Power
(This parameter is not
Distribution
displayed for some
Unit >
distribution units.)
Running
Parameters >
Unhide All
Advanced
Signals >
Power
Distribution
Settings
Copyright © Huawei Technologies Co., Ltd.
Parameter
Default
Name
Value
Upper load
80
current
threshold
Lower load
60
current
threshold
4 Power-On Commissioning
Setting
When the load current
exceeds the preset
value, an alarm is
generated.
When the load current
exceeds the preset
value, an alarm is
generated.
Defaul
Description
t Value
32
Rated current 32 A
for each branch.
46