Connection Configuration In The S7-1500 Cpu - Siemens SIMATIC S5 Manual

Ethernet communication (iso on tcp) between controllers
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

2 Engineering
An enable of the communication is initiated via the startup bit M 180.5
(OB21/22). Thus, this communication is enabled.
Every second (clock memory bit), a count value (DB60) is sent to the S7-1500
via the CP1543-1 using the ISO-on-TCP connection.
After the data have been received, this count value is checked in the S7-1500
and incremented by +1. At the next send trigger of the S7-1500, it is sent back
to the SIMATIC S5. The data received by the SIMATIC S5 are transferred to
DB50.
A simple error analysis regarding the connection status is done by storing the
indicator words and parameter error bytes.
HTB_SEND block: ANZW: MW60 PAFE: MB64
HTB_RECEIVE block: ANZW: MW50 PAFE: MB54
2.6.4

Connection configuration in the S7-1500 CPU

Prerequisite
All network-side settings of the S7-1500 CPU and of the CP1543-1 used in TIA
Portal are structured identically for all scenarios.
For the corresponding configuration steps, proceed as described in chapter
steps 1 and 2 of scenario 1 and complete the configuration following the steps
described in the next section.
Configuration
In this scenario 4a, the connection is parameterized via a dialog in TIA Portal. The
required connection parameter are pre-assigned and set up via a connection table
in the S7-1500 CPU.
3. In the "Device configuration" (1) of the "PLC_Sz4..", open the "Network view"
(2). In the "Connections" tab (3), select your CPU and use the "Insert" menu
item or right-click to add a new connection.
Ethernet Communication (ISO on TCP) between SIMATIC S5 and
SIMATIC S7-1500 Controllers
Entry-ID: 109482475,
V1.2,
1
07/2019
2.2.4
3
2
63