Routine Maintenance - Huawei FusionModule 1000A20 Maintenance Manual

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule 1000A20:
Table of Contents

Advertisement

FusionModule1000A20 Prefabricated All-in-One Data
Center
Maintenance Guide

3.2 Routine Maintenance

Table 3-2 Routine maintenance checklist
Category
ECC800
WebUI
Fire
extinguishing
system
Issue 01 (2019-07-15)
Maintenance
Instructions
Item
FusionModule1
On the ECC800
000A alarms
WebUI, choose
Home > Active
Alarms or
Query >
Historical
Alarms.
Camera images
On the ECC800
and angles
WebUI, choose
System >
Video
Settings >
Video
Information.
Click Access
Link to display
the linked video
page.
VESDA and its
Check the
power supply
working status
of the VESDA
and its power
supply.
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Criteria
Troubleshooti
ng
No alarm is
Clear the alarm
displayed in the
by referring to
alarm
the ECC800
information
documents.
area.
Alarm short
Check whether
message service
the SIM card is
(SMS)
properly
messages can
installed.
be received.
Replace the
SIM card if it is
faulty.
The video
If no video
images are
image is
properly
displayed:
displayed.
1. Connect the
camera
cable again.
2. If the cable
is properly
connected,
replace the
camera.
The coverage of
If camera
the camera is
angles do not
optimal.
meet the
monitoring
requirement,
adjust them by
following the
instructions in
the
commissioning
guide.
The VESDA
If the VESDA
and its power
or its power
supply are
supply is
normal.
abnormal,
troubleshoot by
following
instructions in
documents
delivered with
the VESDA.