Wiring
Between indoor unit and outdoor unit connection cable specifications(Common in use)
Communication cable
0.75mm², 2wires
For the power Cable, use the grade H07RN-F or H05RN-F materials.
1-phase terminal block spec
AC power : M5 screw
17
13
3-phase terminal block spec
AC power : M4 screw
1(L)
2(N)
L1(R)
9.8
34
Power supply cords of parts of appliances for outdoor use shall not be lighter
than polychloroprene sheathed flexible cord. (Code designation IEC:60245
IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F)
When installing the outdoor unit in a computer room or net work room,
server room or in the presence of risk of disturbance to the communication
cable, use the double shielded (tape aluminium / polyester braid + copper )
cable of FROHH2R type.
L
N
L3(T)
L2(S)
N
14.19
Home server
0.75mm², 2wires
Communication : M4 screw
10.1
Communication : M4 screw
10.1