CAUTION
The 100 mm clearances above and below the components must be observed.
CAUTION
The terminals on the voltage limiting network (Voltage Peak Limiter) must always be
connected as follows:
• Cable from the DC link of the Power Module at DCPS, DCNS and
• Cable to the dv/dt reactor 1U2, 1V2, 1W2.
Failure to connect the terminals correctly could damage the voltage peak limiter.
CAUTION
If dv/dt filters plus Voltage Peak Limiters are used that SIEMENS has not approved for
SINAMICS, these dv/dt filters may be damaged.
The surface temperature of the dv/dt reactors may exceed 80 °C.
When a dv/dt filter plus Voltage Peak Limiter is used with SINAMICS G130, the pulse
frequency of the Power Module must not exceed 2.5 kHz/4 kHz. Setting a higher pulse
frequency can lead to destruction of the dV/dt filter.
CAUTION
When a dV/dt filter plus Voltage Peak Limiter is used, the drive must not be operated
without a connected motor, otherwise the filter can be destroyed.
CAUTION
If a dv/dt filter plus Voltage Peak Limiter is connected to the Power Module, it is essential
that it is activated during commissioning (p0230 = 2).
CAUTION
The maximum permissible output frequency when a dv/dt filter with Voltage Peak Limiter is
used is 150 Hz.
dV/dt filter plus Voltage Peak Limiter
Operating Instructions, 03/2012, A5E00692302A