Siemens DMS8000 MP4.30 Connectivity Manual page 19

Sipass access control connectivity
Hide thumbs Also See for DMS8000 MP4.30:
Table of Contents

Advertisement

Configuring SiPass Access Control System
No Alarm Classes defined
Alarm Class of any point type
configured as:
No Acknowledge required
Input Alarm Class configured
as:
- Acknowledge required
- Not Restorable
Input Alarm Class configured
as:
- Acknowledge required
- Restorable
Alarm Class of any other type
but Input configured as:
- Acknowledge required
- Restorable
Alarm Class of any other type
but Input configured as:
- Acknowledge required
- Not Restorable
Building Technologies
Fire Safety & Security Products
The table below presents the possible scenarios and the results for the system op-
erator. Refer to this table for any further needs of Alarm Classes when discussing
the issue with SiPass specialists.
Effect in MM8000/MK8000
Event generation and transactions
(within the documented limitations)
as configured in Composer by
default.
Door alarms received and dis-
played as Severe Alarm.
No additional event.
Event generation; point status is
not visible.
Event closing always possible
regardless of the point status.
Subsequent events from this point
are displayed as new events.
Input activation Advisory never
receives and displays the Inac-
tive point state.
Event generation; point status is
not visible.
Event closing always possible
regardless of the point status.
Re-activated events (triggered
by the Restorable "Once ac-
tioned ... " option) are no more
received.
Input activation Advisory receives
and displays the Inactive point
state.
None
None
Check latest MM8000 Release Notes for version compatibility and limitations.
048_DMS_DMS8000_Connectivity_Access_Control_MP4.30_A6V10062451_a_en
Effect in SiPass
No alarm pop-ups.
Registrations in audit trail.
No alarm pop-up.
Registrations in audit trail.
No alarm pop-up of this input.
Registrations in audit trail.
No alarm pop-up of this input initial
event.
Re-activated pop-ups are displayed
if the input remains active.
Registrations in audit trail.
Alarm pop-up not removable 
"freezing" SiPass client.
Alarm pop-up
Registrations in audit trail.
17
06.2010

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dms8000 mp4.15

Table of Contents