Chapter 7 Maintenance

7.2 Checking the Status Information

When there is an error in the CIF module, an error code is stored in the CIF module
internal status (0W).
Status
RDY ERR
[0W]
Error
code
01H
02H
03H
04H
05H
10H
26
F
E
D
C
B
No use
Bit
Name
F
RDY
1:Normal operation
ready
0:Initializing or error occuring
E
ERR
1:Error
error
0:No error
Type
CPU error
CPU error has been detected
during initialization.
ROM error
ROM error has been
detected during initialization.
Work RAM error
RAM error has been detected
during initialization.
Common memory
Common memory error has
error
been detected during
initialization.
Switch setting error
Switch setting error has been
detected during operation.
WD timer error
Watchdog timer error has
been detected during
operation.
A
9
8
7
6
Description
Description
model 2000 CIF Module (CF611)User's Manual
5
4
3
2
1
Error code
Status
Replace the CIF module.
・ ERR bit turns ON.
・ Module operation is
stopped.
Press the reset button and
check whether recovery is
possible. If it still occurs,
replace the CIF module.
・ ERR bit turns ON.
・ Module operation is
stopped.