NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Menu
System Settings
(visible for
V200R002
version)
T/H sensor
(visible for
V200R002
version)
Issue 07 (2020-03-16)
Parameter
Description
this group
can be set).
Number of
Number of active
running
units in a group. The
smart cooling
value ranges from 1
products in
to Number of smart
this group
cooling products in
this group.
Humidifying
The humidifying
function
function can be set
to Enable, Disable,
or Enabled when
active power.
Dehumidifyi
The dehumidifying
ng function
function can be set
to Enable, Disable,
or Enabled when
active power.
Temperature
Cold aisle, Hot
and humidity
aisle, Return air, or
control type
Supply air can be
set as required. The
temperature and
humidity set points
correspond to the
selected control type
can be set.
Copyright © Huawei Technologies Co., Ltd.
4 Commissioning
Configuration Principle
The host allocates running units
by smart cooling product unit
address in ascending order,
which is from 1 to 32. The rest
will become the standby ones.
Enable indicates that the
electric humidifier will be
started when the ambient
humidity is lower than the
certain humidity range of the
humidity set point. Disable
indicates that the electric
humidifier will not be started.
Enabled when active power
indicates that the electric
humidifier will be started when
the main power is active and the
ambient humidity is lower than
the certain humidity range of the
humidity set point.
Enable indicates that the
dehumidification function will
be enabled when the ambient
humidity exceeds the certain
humidity range of the humidity
set point. Disable indicates that
the dehumidification function
will not be enabled. Enabled
when active power indicates
that the dehumidification
function will be enabled when
the main power is active and the
ambient humidity exceeds the
certain humidity range of the
humidity set point.
When the application
scenario is cold or hot aisle
containment, you are advised
to choose Cold aisle if the
cold aisle T/H sensors are
configured, and choose
Supply air if the cold aisle
T/H sensors are not
configured.
When the application
scenario is non-aisle
containment, you are advised
to choose Return air, and
67