7
ONLINE MODULE CHANGE
7 - 17
(c)
Click the [Close] button to close the System monitor screen.
(d)
Set a digital value to CH
Un\G1, Un\G2), and turn on and off Operating condition setting request
(Y9). Turn on CH
used, and check whether proper conversion has been made or not.
(Be careful since analog outputs are provided actually.)
(5) Resumption of control
(a)
After choosing [Diagnosis] - [Online module change] on GX Developer to
display the "Online module change" screen again, click the [Execution]
button to resume control. Module ready (X0) turns on.
(b)
The "Online module change completed." screen appears.
Digital value (buffer memory address 1, 2:
Output enable/disable flag (Y1, Y2) of a channel to be
MELSEC-Q
7 - 17