Shielded Lines; General Shielding Principle - Honeywell ACS-2plus Installation Instructions Manual

Table of Contents

Advertisement

12
5.2

Shielded lines

-
Die ACS-2 plus devices are daisy chained via a shielded line.
Use cables of category Cat 5 or higher!
-
The shielding of the incoming line is to be connected to the shield soldering bar of the ACS-2 plus. The
shielding of the outgoing line is not connected.
-
The shield terminal bar in each ACS-2 plus must be connected to a separate PE.
(min. cable cross-section 1,5mm²)
If, when using 12V devices, it is technically not possible to connect ground potential to each ACS-2 plus,
it is recommended to use a three wire cable for the power supply. The third core carries the ground
potential of the common power supply unit. This wire is connected to the shield terminal bar in each ACS-
2 plus. This method is only a temporary solution and should only be used in exceptional cases.
-
The shielding of the reader line is connected on one side to the shield terminal bar in the ACS-2 plus.
-
The above mentioned points also principally apply to the ACS-2 plus module bus .