Initial Setting (Software); Binding & Commissioning (Notice); Led Display (D19) - Fujitsu Airstage UTY-VLGX Installation Manual

Network convertor
Hide thumbs Also See for Airstage UTY-VLGX:

Advertisement

7.
Turn the power off and on or press SW7 (reset button)
to exit from address setting mode.
This time, please refer to the "7. TURNING ON THE
POWER" for the content displayed in D19 LED.
91

INITIAL SETTING (SOFTWARE)

The initial settings for the Network Convertor must be per-
formed before the commissioning. Please see the attached
"Application Manual - Tool for Network Convertor" and
complete the settings.
101
BINDING & COMMISSIONING (NOTICE)
It is necessary to make an XIF (External Interface
(1)
File) for binding.
(2)
The commissioning doesn't end if the number of
Indoor/Outdoor Unit of the XIF file made with Tool
of Network Convertor is not in consistency with
the number after Indoor/Outdoor Unit Address is
registered.
In addition, the Network Convertor can not oper-
ate normally if the number of Indoor/Outdoor Unit
of the XIF file is not in consistency with the num-
ber after Indoor/Outdoor Unit Address is regis-
tered.
(3)
Binding and commissioning must be performed
again if the number of connecting units (indoor/
outdoor units) has changed after system op-
eration. Please always register the allocation
information that is in consistency with the VRF
system, Functional Block in the Network Con-
vertor and the Network Convertor, if register the
changed XIF file in according to the "Tool for
Network Convertor".
Important:
Network Convertor will not operate if,
VRF network system address (Indoor & Outdoor units ad-
dress) allocation information are not registered to Net-
work Convertor.
XIF data information and VRF network system address
allocation information must not be same.
Binding & Commissioning is not executed.
The ID number registered on Network Convertor is differ-
ent from the ID number when XIF file is created.
Two or more Network Convertors are connected to BMS,
and these are set the same ID number.
111

LED DISPLAY (D19)

(1) Normal code
Normal code
Normal mode
Set state of "Tool for Network Con-
vertor"
Address setting mode
Under maintenance
FB and unit address allocation
information is registered with
"Tool for Network Convertor"
(2) Error code
Error code
FB and unit address allocation
information is not registered
Main PCB error
VRF Network error
D9 LED lit or blinking
Communication error
(Error of the Network Interface De-
D9
D9
vice on VRF System)
D14 LED lit or blinking
Communication error
(Error of the Network Interface De-
D14
D14
vice on BMS)*1
When V series or S series is con-
nected
*1.
D14 is ON for 1 second, OFF for 1 second, and repeats. When
D19 is in Normal mode, Commissioning is unset.
Contents
FB* : Functional Blocks
Contents
En-6